GE IS200ACLEH1CAA Application Control Layer Module
The GE IS200ACLEH1CAA, also cataloged as the IS200ACLEH1CAA Application Control Layer Module, operates as a dedicated hardware component for deterministic excitation control execution within GE Mark VI and EX2100 Excitation Control Systems. The module provides processor-based task management, communication handling, and control processing through a 100 MHz CPU, onboard memory, and system interface channels.
Hardware Specifications
Parameter
Specification
Model
IS200ACLEH1CAA
Brand
GE
Origin
United States
Weight
1.3 kg
Operating Temp
-30 to +65 deg C
Power Consumption
5 VDC backplane supply
Product Type
Application Control Layer Module
System Platform
Mark VI / EX2100 Excitation Control System
Processor
Intel 486 CPU, 100 MHz
Memory
8 MB DRAM, 4 MB Flash
Cache
128 KB L2 cache
Communication Interfaces
Ethernet, ISBus, COM1/COM2 serial ports
Input Voltage
125 VDC
Output Voltage
24 VDC
Mounting Type
DIN-rail or exciter backplane slot
Deterministic Control and Firmware Execution
The IS200ACLEH1CAA uses a microprocessor-based architecture for execution of excitation control tasks, communication processing, and system synchronization functions. The 4 MB Flash memory stores firmware and configuration data, while the DRAM supports runtime processing requirements. The module manages Ethernet communication, ISBus synchronization, and serial interface operations within the Mark VI control architecture.
Frequently Asked Questions
Q: What communication interfaces are supported by the IS200ACLEH1CAA? A: The module supports Ethernet, ISBus, and COM1/COM2 serial communication interfaces for control system data exchange and diagnostics.
Q: What power supply requirements apply to this module? A: The module operates with a 125 VDC input system interface and uses a 5 VDC backplane supply for internal module operation.
Q: Is the IS200ACLEH1CAA compatible with EX2100 excitation systems? A: The module is designed for installation in GE EX2100 exciter racks and Mark VI control system architectures.
Field Installation Guidelines
Verify cabinet power isolation before module replacement or installation. Use ESD protection equipment when handling the circuit board assembly. Install the module into the assigned exciter backplane slot or DIN-rail mounting position according to rack configuration requirements.
Route Ethernet, ISBus, and serial cables separately from high-voltage power conductors to reduce electromagnetic interference. Ensure cable shielding is connected according to cabinet grounding practices. Confirm backplane seating, connector engagement, and firmware compatibility before system energization.