Lebih dari 100.000 Suku Cadang PLC, DCS, Drive, TSI & MRO Tersedia Pelajari lebih lanjut

ICS Triplex T8403C Trusted TMR 24 VDC Digital Input Module

ICS Triplex T8403C Trusted TMR 24 VDC Digital Input Module

Formulir produk

ICS Triplex T8403C Trusted TMR 24 VDC Digital Input Module Configured for 24 VDC digital signal acquisition in the Trusted... Baca selengkapnya

SKU: T8403C
Negara asal: USA

      100% Asli dan Autentik

    Butuh stok banyak? Hubungi kami .

      100% Baru, Siap kirim

    Butuh stok banyak? Hubungi kami .

      Dukungan Pengembalian Dana, Layanan 7X24 jam

    Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .

      Hubungi kami: +86 135 995 07613

    Tersedia pada hari kerja antara pukul 09.00 hingga 18.00

      Email kami: sales2@industriaxplc.com

    Tersedia 24/7 untuk pertanyaan dan dukungan

    Keterangan

    ICS Triplex T8403C Trusted TMR 24 VDC Digital Input Module

    Configured for 24 VDC digital signal acquisition in the Trusted TMR I/O architecture, the ICS Triplex T8403C (T8403C Input Module) provides 40 discrete input channels with configurable thresholds and 50 V reinforced field isolation.

    Hardware Specifications

    Parameter Specification
    Model T8403C
    Brand ICS Triplex
    Product Type Trusted TMR 24 VDC Digital Input Module
    Origin USA
    Weight 1.15 kg
    Dimensions 3 x 30.3 x 26.4 cm estimated shipping size
    Operating Temp Not specified in supplied data
    Power Consumption Maximum power dissipation: 29 W
    Number of Inputs 40
    Input Type Digital Input
    Nominal Field Voltage 24 VDC
    Field Commo 50 V reinforced
    Impedance 5 kOhm
    Measurement Range -6 to +36 VDC
    Input Thresholds Configurable
    Maximum Withstanding Voltage +/-50 VDC
    Safety Accuracy 0.5 VDC
    Field Connection 3-wire field device connection
    Field Power Fused field power supply per channel
    Mounting DIN rail compatible
    Redundancy Architecture Triple Modular Redundancy (TMR)
    Inter-Module Bus IMB
    Status Indicators 3 Healthy, 1 Active, 1 Standby, 1 Educated

    TMR Safety Architecture and Digital Input Processing

    The T8403C uses a Triple Modular Redundancy (TMR) architecture for digital input acquisition. Each module contains three module slices that process the input data independently.

    The Field Processing Unit (FPU) receives data from the three slices and performs a 2oo3 vote on each input data bit. Therefore, the voting process determines the reported input state from redundant processing paths.

    The module interfaces with the Trusted Inter-Module Bus (IMB), which distributes module power and communication with the Trusted TMR Processor. In addition, the field interface provides direct connections for the external digital input circuits.

    The supplied data specifies 50 V reinforced field isolation. Furthermore, each channel incorporates a fused field power supply, while the field interface supports 3-wire device connections.

    The front panel provides six status LEDs. Three Healthy indicators correspond to the individual module slices, while Active, Standby, and Educated indicators are controlled by the FPU.

    Frequently Asked Questions (FAQ)

    Q: How many digital inputs does the ICS Triplex T8403C provide?
    A: The T8403C provides 40 digital input channels per VFTA.

    Q: How does the T8403C process redundant input data?
    A: Three module slices process the input data, and the FPU performs a 2oo3 vote on each data bit.

    Q: What input voltage range does the T8403C specify?
    A: The supplied specification lists a measurement range of -6 to +36 VDC, with configurable input thresholds and +/-50 VDC maximum withstanding voltage.

    Field Installation Guidelines

    • Install the T8403C according to the applicable Trusted system hardware installation requirements.
    • Verify the field wiring before energizing the module. Confirm correct polarity and terminal allocation for each digital input.
    • Use the specified 3-wire field connection arrangement where applicable.
    • Keep field signal wiring separated from high-voltage power and high-current switching conductors to reduce electrical interference.
    • Connect cable shields according to the plant grounding and control-system wiring standard. Avoid creating unintended ground loops.
    • Verify the field supply voltage remains within the specified input measurement range before connecting external devices.
    • Check each channel fuse and field power circuit before commissioning.
    • Confirm the three Healthy indicators and the Active, Standby, and Educated status indicators after installation.
    • Do not apply voltages beyond the stated +/-50 VDC maximum withstanding specification.
    • Confirm correct IMB seating and module engagement before system startup.

    Spesifikasi

    • Merek: ICS Triplex

    • :

    Keuntungan

    • Keandalan tinggi di lingkungan industri

    • Mendukung operasi berkelanjutan
    • Kompatibel dengan sistem PLC/DCS utama

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Kirimkan pesan kepada kami!

    Butuh stok banyak? Hubungi kami.

    Koleksi yang mungkin Anda sukai

    Produk yang baru saja dilihat

      Login

      Lupa kata sandi Anda?

      Belum punya akun?
      Buat akun