Honeywell MC-TAIH22 High-Level Analog Input Field Termination Assembly The Honeywell MC-TAIH22 51204170-150, also cataloged as the MC-TAIH22 High-Level Analog Input...
Baca selengkapnya
Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .
Hubungi kami: +86 135 995 07613
Tersedia pada hari kerja antara pukul 09.00 hingga 18.00
Email kami: sales2@industriaxplc.com
Tersedia 24/7 untuk pertanyaan dan dukungan
Keterangan
Honeywell MC-TAIH22 High-Level Analog Input Field Termination Assembly
The Honeywell MC-TAIH22 51204170-150, also cataloged as the MC-TAIH22 High-Level Analog Input Field Termination Assembly, operates as a dedicated hardware component for analog signal conditioning and acquisition within Honeywell Process Manager and Experion PKS I/O systems.
Hardware Specifications
Parameter
Specification
Model
MC-TAIH22 51204170-150
Brand
Honeywell
Origin
USA
Product Type
High-Level Analog Input Field Termination Assembly
Input Channels
16 analog input channels
Supported Input Signals
4-20 mA, 0-10 VDC, 1-5 VDC high-level analog signals
A/D Resolution
12-bit analog-to-digital conversion
Accuracy
+/- 0.25% of full scale
Terminal Interface
Compression screw terminals
Isolation
Channel-to-system electrical isolation
Conformal Coating
Available depending on hardware revision
Mounting Type
DIN rail or Honeywell cabinet mounting
Weight
Approximately 0.8 kg
Dimensions
Approximately 20 cm x 12.7 cm x 5 cm
Operating Temp
0 deg C to +60 deg C
Power Consumption
Field termination assembly power consumption based on system I/O configuration
Process Control Signal Conditioning and Isolation
The MC-TAIH22 processes high-level analog field signals before transmission to Honeywell Process Manager and Experion PKS control platforms. The assembly accepts standard transmitter outputs, including 4-20 mA current loops and voltage inputs, then performs signal termination, filtering, and electrical isolation.
For Honeywell process control applications, the module supports channel-to-channel isolation principles to reduce interference between independent field loops. Additionally, the hardware configuration allows integration with analog measurement devices using HART-based 4-20 mA loop communication when the connected I/O architecture supports transmitter communication functions.
The module design supports stable analog acquisition for variables such as pressure, temperature, flow, and level measurement. Therefore, proper shielding, grounding, and signal routing practices directly affect measurement quality in industrial installations.
Frequently Asked Questions
Q: Does the MC-TAIH22 support direct connection of 4-20 mA transmitters? A: Yes. The assembly supports high-level analog inputs from 4-20 mA transmitters and other compatible voltage signal sources through its field termination channels.
Q: Does the MC-TAIH22 provide electrical isolation between field channels and the control system? A: Yes. The module provides channel-to-system electrical isolation for connected analog signal paths.
Q: Can the MC-TAIH22 be installed as a standalone analog input controller? A: No. The MC-TAIH22 functions as a field termination assembly and requires connection to the corresponding Honeywell Process Manager or Experion PKS I/O hardware.
Field Installation Guidelines
Install the MC-TAIH22 inside the specified Honeywell cabinet or approved DIN rail mounting location.
Connect analog field wiring using shielded instrumentation cables where required by the installation design.
Terminate cable shields according to the site grounding standard to reduce electrical noise coupling.
Separate analog signal wiring from high-voltage power cables and switching circuits.
Verify field loop polarity before applying system power.
Confirm the configured input type matches the connected transmitter output range before commissioning.
Inspect terminal connections periodically to maintain proper mechanical contact.