Lebih dari 100.000 Suku Cadang PLC, DCS, Drive, TSI & MRO Tersedia Pelajari lebih lanjut

Honeywell 900U02-0100 Universal I/O Module

Honeywell 900U02-0100 Universal I/O Module

Formulir produk

Honeywell 900U02-0100 Universal I/O Module Configured for configurable analog and digital signal processing in the Honeywell ControlEdge HC900 platform, the... Baca selengkapnya

SKU: 900U02-0100
Negara asal: USA

      100% Asli dan Autentik

    Butuh stok banyak? Hubungi kami .

      100% Baru, Siap kirim

    Butuh stok banyak? Hubungi kami .

      Dukungan Pengembalian Dana, Layanan 7X24 jam

    Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .

      Hubungi kami: +86 135 995 07613

    Tersedia pada hari kerja antara pukul 09.00 hingga 18.00

      Email kami: sales2@industriaxplc.com

    Tersedia 24/7 untuk pertanyaan dan dukungan

    Keterangan

    Honeywell 900U02-0100 Universal I/O Module

    Configured for configurable analog and digital signal processing in the Honeywell ControlEdge HC900 platform, the Honeywell 900U02-0100 (900U02 Universal I/O Module) provides direct physical and electrical execution. The module supports software-selectable AI, AO, DI, and DO functions on each channel, accepts 4-20 mA process signals with HART communication support, and incorporates line monitoring, short-circuit protection for digital outputs, and configurable redundancy for process control applications.

    Hardware Specifications

    Parameter Specification
    Model 900U02-0100
    Brand Honeywell
    Product Type Universal I/O Module
    Origin USA
    Place of Shipment Xiamen, China
    Weight 0.2 kg
    Dimensions 13.4 x 3.3 x 5.4 cm
    Field Supply Voltage 24 VDC
    Non-redundant Configuration 16 channels
    Redundant Configuration 14 channels
    Input Channels Maximum 16 per module
    Input Range 4-20 mA
    A/D Converter Resolution 16 bit
    Update Rate 10 ms
    Channel Load 500 mA per channel
    Maximum Module Load 4.2 A
    ESCP Protection 620 mA resettable
    Input Impedance 250 Ohm nominal
    Crosstalk 58 dB, DC to 60 Hz, channel-to-channel
    Output Current Range 2.4 mA to 21 mA, directly configurable
    Maximum Resistive Load 7504 Ohm
    Digital Output Protection Short-circuit protection
    HART Support Supported
    Channel Configuration AI, AO, DI, or DO by software
    Line Monitoring Available for all configurations

    4-20 mA HART Loop and Channel Configuration

    The module supports standard 4-20 mA process loops together with HART communication, allowing analog measurement and digital device communication over the same wiring pair. Each channel can be configured independently through software as an analog input, analog output, digital input, or digital output without hardware replacement.

    The 16-bit A/D converter provides digital conversion for analog input signals, while the nominal 250 Ohm input impedance matches standard current-loop installations. In addition, the module maintains 58 dB channel-to-channel crosstalk performance from DC to 60 Hz, reducing interference between adjacent channels during mixed signal operation.

    Digital output channels include integrated short-circuit protection, and line monitoring remains available regardless of the selected I/O configuration. Therefore, the same hardware platform can support different field signal combinations while maintaining a common wiring architecture.

    Frequently Asked Questions

    Q: Does the 900U02-0100 require different hardware for AI, AO, DI, and DO functions?
    A: No. Each channel is software configurable as an analog input, analog output, digital input, or digital output according to the control strategy.

    Q: Does the module support HART field instruments?
    A: Yes. The module supports HART communication on compatible 4-20 mA loops.

    Q: Can all 16 channels remain available in a redundant installation?
    A: No. The module supports 16 channels in a non-redundant configuration and 14 channels when configured for redundancy.

    Field Installation Guidelines

    • Verify that the field supply provides 24 VDC before connecting field wiring.
    • Separate analog signal cables from high-voltage or motor power cables to reduce electrical noise.
    • Connect cable shields according to the plant grounding specification to minimize electromagnetic interference.
    • Confirm channel configuration before energizing field devices because each channel can operate as AI, AO, DI, or DO.
    • Ensure that field current and resistive loads remain within the specified module ratings.
    • Inspect terminal wiring after installation and verify loop continuity before placing the module into service.

    Spesifikasi

    • Merek: Honeywell

    • :

    Keuntungan

    • Keandalan tinggi di lingkungan industri

    • Mendukung operasi berkelanjutan
    • Kompatibel dengan sistem PLC/DCS utama

    Customer Reviews

    Be the first to write a review
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    0%
    (0)
    Kirimkan pesan kepada kami!

    Butuh stok banyak? Hubungi kami.

    Koleksi yang mungkin Anda sukai

    Produk yang baru saja dilihat

      Login

      Lupa kata sandi Anda?

      Belum punya akun?
      Buat akun