Lebih dari 100.000 Suku Cadang PLC, DCS, Drive, TSI & MRO Tersedia Pelajari lebih lanjut

GE Multilin 369-HI-R-M-0-P-0-E Motor Protection Relay

GE Multilin 369-HI-R-M-0-P-0-E Motor Protection Relay

Formulir produk

GE Multilin 369-HI-R-M-0-P-0-E Motor Protection Relay The GE Multilin 369-HI-R-M-0-P-0-E, also cataloged as the 369 Motor Protection Relay, operates as a dedicated hardware... Baca selengkapnya

SKU: 369-HI-R-M-0-P-0-E
Negara asal: USA

      100% Asli dan Autentik

    Butuh stok banyak? Hubungi kami .

      100% Baru, Siap kirim

    Butuh stok banyak? Hubungi kami .

      Dukungan Pengembalian Dana, Layanan 7X24 jam

    Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .

      Hubungi kami: +86 135 995 07613

    Tersedia pada hari kerja antara pukul 09.00 hingga 18.00

      Email kami: sales2@industriaxplc.com

    Tersedia 24/7 untuk pertanyaan dan dukungan

    Keterangan

    GE Multilin 369-HI-R-M-0-P-0-E Motor Protection Relay

    The GE Multilin 369-HI-R-M-0-P-0-E, also cataloged as the 369 Motor Protection Relay, operates as a dedicated hardware component for three-phase motor protection, thermal monitoring, metering, and diagnostic execution within GE Multilin 369 motor protection systems.

    Hardware Specifications

    Parameter Specification
    Model 369-HI-R-M-0-P-0-E
    Brand GE Multilin / General Electric
    Origin United States
    Operating Temp -40 deg C to +60 deg C
    Power Consumption Not specified in available documentation
    Control Power Supply 90-300 VDC / 70-265 VAC, 50/60 Hz
    Phase Current Inputs 1 A or 5 A secondary CT inputs, field selectable
    Ground Current Inputs 1 A / 5 A CT or 50:0.025 zero-sequence CT
    Voltage Inputs Up to 600 VAC direct input or VT ratio configuration
    Frequency Range 20 to 70 Hz
    RTD Inputs 12 RTD inputs
    Protection Functions Thermal overload, phase overcurrent, ground fault, undercurrent, voltage protection, stall and acceleration protection
    Enclosure Protection NEMA 12 / IP54 front panel
    Environmental Protection Conformal coated PCB construction

    GE Multilin 369 Thermal Model and Motor Monitoring Functions

    The GE Multilin 369 series uses a dynamic thermal model with motor thermal capacity utilization (TCU) calculation for overload protection. The relay processes current imbalance, ambient temperature compensation, and motor operating conditions to calculate thermal stress during startup and running states.

    The relay supports motor condition evaluation through real-time electrical measurement including voltage, current, frequency, power, energy, and power factor values. Optional metering functions provide additional operational data acquisition for motor load analysis.

    The protection logic includes instantaneous and timed phase overcurrent elements, sensitive ground fault detection through residual or core balance CT connections, undercurrent monitoring for loss-of-load conditions, and stall protection for locked rotor or mechanical jam conditions.

    Frequently Asked Questions

    Q: Does the 369-HI-R-M-0-P-0-E support remote display operation?
    A: Yes. The R suffix indicates a remote display configuration with enhanced faceplate interface and keypad functionality.

    Q: What current transformer inputs are supported by this relay?
    A: The relay accepts field-selectable 1 A or 5 A secondary phase CT inputs and supports ground CT configurations including zero-sequence CT connections.

    Q: Can the relay communicate through industrial protocols?
    A: The 369 platform supports optional communication interfaces, including PROFIBUS-DP protocol options depending on installed configuration.

    Field Installation Guidelines

    Install the relay in a compatible protective relay enclosure with suitable ventilation and environmental control. Verify control power polarity and voltage range before energizing the unit.

    Terminate CT wiring according to protection relay installation practices. Maintain proper polarity between current transformers and relay input terminals. Use shielded wiring for low-level measurement and communication circuits, with cable shields grounded according to site grounding procedures.

    Separate power conductors from signal wiring to reduce electrical noise coupling. Verify RTD wiring continuity and sensor identification before commissioning. Confirm relay configuration parameters, motor ratings, CT ratios, and protection thresholds before placing the motor circuit into service.

    Spesifikasi

    • Merek: General Electric

    • :

    Keuntungan

    • Keandalan tinggi di lingkungan industri

    • Mendukung operasi berkelanjutan
    • Kompatibel dengan sistem PLC/DCS utama