GE IS200VTURH1BAB Primary Turbine Protection Board

GE IS200VTURH1BAB Primary Turbine Protection Board

Formulir produk

GE IS200VTURH1BAB Primary Turbine Protection Board Configured for turbine overspeed monitoring and emergency trip execution in GE Mark VI Speedtronic... Baca selengkapnya

SKU: IS200VTURH1BAB
Negara asal: USA

      100% Asli dan Autentik

    Butuh stok banyak? Hubungi kami .

      100% Baru, Siap kirim

    Butuh stok banyak? Hubungi kami .

      Dukungan Pengembalian Dana, Layanan 7X24 jam

    Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .

      Hubungi kami: +86 135 995 07613

    Tersedia pada hari kerja antara pukul 09.00 hingga 18.00

      Email kami: sales2@industriaxplc.com

    Tersedia 24/7 untuk pertanyaan dan dukungan

    Keterangan

    GE IS200VTURH1BAB Primary Turbine Protection Board

    Configured for turbine overspeed monitoring and emergency trip execution in GE Mark VI Speedtronic systems, the GE IS200VTURH1BAB (IS200VTUR Primary Turbine Protection Board) provides direct physical/electrical execution for speed signal acquisition, flame detector monitoring, and trip relay control functions. The board processes magnetic pickup inputs, voltage monitoring channels, and protection signals for turbine shutdown logic.

    Hardware Specifications

    Parameter Specification
    Model IS200VTURH1BAB
    Brand GE
    Origin United States
    Weight 0.5 kg
    Dimensions 11 x 9 x 3 inches
    Operating Temp 0 deg C to +60 deg C
    Power Consumption 125 VDC operational input
    Product Type Primary Turbine Protection Boards
    System Platform GE Mark VI Speedtronic Turbine Control System
    Analog Inputs 6 voltage monitoring channels
    Speed Inputs 4 passive magnetic pickup inputs
    Frequency Range 2 Hz to 20 kHz
    Minimum Speed Detection 2 RPM turning gear measurement
    Flame Detector Inputs 8 Geiger-Mueller inputs
    Trip Relay Outputs 3 primary overspeed trip relays
    Signal Resolution 16-bit precision measurement
    Response Time Less than 50 ms for trip initiation
    Common Mode Range +/-5 V signal tolerance
    Redundancy Support Simplex and TMR configurations

    Profinet / EtherNet-IP Deterministic Networks and Protection Signal Handling

    The GE IS200VTURH1BAB performs turbine protection signal processing through dedicated hardware channels within the Mark VI Speedtronic architecture. The board receives speed feedback from passive magnetic pickups, processes frequency measurement signals, and controls overspeed trip relay outputs based on configured protection logic.

    The module supports simplex and triple modular redundancy (TMR) system configurations. In TMR arrangements, protection decisions are coordinated through redundant hardware paths to maintain continuous turbine shutdown monitoring. The board also processes flame detector inputs and shaft voltage/current monitoring signals for protection status evaluation.

    Frequently Asked Questions

    Q: What type of speed input signals are supported by the IS200VTURH1BAB?
    A: The board supports four passive magnetic pickup inputs with a measurable frequency range of 2 Hz to 20 kHz for turbine speed monitoring.

    Q: Does the IS200VTURH1BAB support redundant turbine protection architectures?
    A: Yes. The board supports both simplex and TMR configurations within the GE Mark VI Speedtronic control system.

    Q: What is the function of the trip relay outputs on this board?
    A: The three primary overspeed trip relays provide electrical switching outputs for initiating turbine shutdown actions when protection limits are exceeded.

    Field Installation Guidelines

    Install the IS200VTURH1BAB in the designated GE Mark VI rack location according to the turbine control cabinet hardware arrangement. Verify that terminal boards, field wiring, and rack connections match the configured simplex or TMR architecture before energizing the system.

    Route magnetic pickup, flame detector, and analog monitoring cables separately from high-voltage switching conductors to reduce electrical interference. Use appropriate shield termination practices for low-level measurement circuits and connect cable shields according to the cabinet grounding design.

    Before operation, verify input channel assignment, relay output wiring, and protection signal polarity. Confirm that all field devices connected to the board provide signals within the specified electrical input range.

    Spesifikasi

    • Merek: General Electric

    • :

    Keuntungan

    • Keandalan tinggi di lingkungan industri

    • Mendukung operasi berkelanjutan
    • Kompatibel dengan sistem PLC/DCS utama