GE DS200RTBAG2AHC Relay Terminal Board The GE DS200RTBAG2AHC, also cataloged as the DS200RTBA Relay Terminal Board, operates as a dedicated hardware component for...
Baca selengkapnya
Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .
Hubungi kami: +86 135 995 07613
Tersedia pada hari kerja antara pukul 09.00 hingga 18.00
Email kami: sales2@industriaxplc.com
Tersedia 24/7 untuk pertanyaan dan dukungan
Keterangan
GE DS200RTBAG2AHC Relay Terminal Board
The GE DS200RTBAG2AHC, also cataloged as the DS200RTBA Relay Terminal Board, operates as a dedicated hardware component for relay signal isolation and field device switching within GE Mark V Speedtronic turbine control systems.
Hardware Specifications
Parameter
Specification
Model
DS200RTBAG2AHC
Brand
GE
Origin
United States
Weight
0.3 kg
Dimensions
23 cm x 15 cm x 1.6 mm
Operating Temp
0 to +55 deg C
Power Consumption
Not specified; 24 VDC relay coil operation
Board Type
Relay Terminal Board (RTBA)
System Platform
GE Mark V Speedtronic turbine control system
Relay Quantity
10 electromechanical relays
Relay Configuration
7 DPDT relays with 2 Form-C contacts, 3 4PDT relays
Coil Voltage
24 VDC
Relay Contact Rating
5 A at 250 VAC / 30 VDC
Response Time
Approx. 10 ms typical
Mechanical Life
10 million operations
Electrical Life
100,000 operations at rated load
Protection
130 VAC MOV protection per relay
Indicators
Individual relay diagnostic lamps
Connectors
2 x 20-pin headers and 1 terminal block
PCB Construction
4-layer FR-4 PCB with approx. 95 components and 8 ICs
Mounting
4 x M4 screw holes with standoffs
GE Mark V Relay Interface and Switching Characteristics
The DS200RTBAG2AHC provides relay expansion and switching functions between Mark V controller logic circuits and external field devices. The relay channels isolate low-voltage control signals from actuator, solenoid, interlock, and protection circuits.
The board follows GE industrial control hardware architecture with relay status indication, configurable jumper settings, and field wiring terminals. Each relay channel includes MOV-based surge suppression to reduce transient effects generated by inductive loads.
The relay interface supports deterministic signal execution in Mark V control systems, where relay output states are coordinated through controller I/O processing and turbine protection logic. The board design supports I/O density scaling by adding multiple switched outputs without modifying the primary controller backplane structure.
Frequently Asked Questions
Q: What relay configurations are available on the DS200RTBAG2AHC? A: The board contains 10 electromechanical relays, including 7 DPDT relays with 2 Form-C contacts and 3 4PDT relays.
Q: What voltage is required for relay coil activation? A: The relay coils operate at 24 VDC.
Q: How are relay outputs protected from voltage transients? A: Each relay channel includes MOV protection for surge suppression associated with field switching loads.
Field Installation Guidelines
Install the DS200RTBAG2AHC in the designated GE Mark V cabinet location with control power removed before handling the PCB.
Verify relay terminal assignments, connector seating, jumper configuration, and mounting hardware before energizing the system. Separate relay field wiring from sensitive analog signal cables and high-current conductors to reduce electrical interference.
Connect cable shields according to the cabinet grounding design. Confirm external device voltage levels match the relay contact and coil specifications before commissioning. Inspect relay indicators during functional testing to verify switching status and field circuit response.