GE DS200DTBAG1A Digital Contact Terminal Board
Configured for discrete contact input termination in the Speedtronic Mark V / Mark V LM control system, the GE DS200DTBAG1A (DS200DTBA Digital Contact Terminal Board) provides direct electrical signal routing between field devices and the digital I/O processing hardware. The board supports up to 46 contact input channels, interfaces with the TCDA processor board for optical isolation, and accepts contact interrogation voltages from 24 V DC to 125 V DC.
Hardware Specifications
Parameter
Specification
Model
DS200DTBAG1A
Brand
GE
Origin
General Electric
Product Type
Digital Contact Terminal Board
Series
Speedtronic Mark V / Mark V LM
Functional Acronym
DTBA
Functional Revision
A (G1A)
Contact Input Capacity
46 digital contact inputs
Input Voltage
24 V DC to 125 V DC
Terminal Blocks
2 screw terminal blocks (TB1, TB2), up to 95 terminal positions
Optical Isolation
Via TCDA Digital I/O processor board
SOE Resolution
1 ms (with TCDA board)
PCB Coating
Normal conformal coating
Connectors
JQR, J12, JY, JQS/T
Operating Temp
-30 deg C to +65 deg C
Weight
1.00 lb
Backplane Communication and Firmware Compatibility
The DS200DTBAG1A functions as a field termination interface rather than an independent processing module. Digital contact states are transferred through the JQR connection to the TCDA Digital I/O processor, where optical isolation and sequence-of-events processing are performed. The J12 connector supplies 125 V DC distribution power, while the JY connector extends the same distribution to an auxiliary DTBB terminal board when system expansion is required. Firmware execution is handled by the associated controller and processor boards; this terminal board does not contain field-upgradable firmware.
Frequently Asked Questions
Q: Does the DS200DTBAG1A support hot swapping while the Mark V system is energized? A: The available documentation does not specify hot-swap capability. Installation or replacement should be performed with the associated control cabinet de-energized and in accordance with the system maintenance procedure.
Q: How is electrical isolation implemented for digital contact inputs? A: Contact signals are routed through the terminal board to the TCDA Digital I/O processor board, where optical isolation is provided before signal processing.
Q: Can different field contact voltages be connected to the board? A: The board supports contact interrogation voltages from 24 V DC to 125 V DC. Voltage selection and wiring should follow the applicable Mark V system configuration and wiring documentation.
Field Installation Guidelines
Verify the DS200DTBAG1A part number and revision before installation.
Isolate cabinet power before connecting or disconnecting field wiring.
Terminate field conductors on TB1 and TB2 using the designated terminal assignments.
Route input wiring separately from high-power conductors to reduce electrical noise.
Maintain proper cable shield grounding according to the control cabinet grounding practice, avoiding multiple shield ground points unless specified by the system design.
Confirm jumper positions before commissioning, particularly when ground isolation is required for troubleshooting.
Inspect the conformal-coated PCB for contamination or mechanical damage before installation.
Verify connector engagement for JQR, J12, JY, and JQS/T before energizing the control system.