Honeywell FS-TDO-1624 Digital Output Module Configured for 24 VDC digital signal execution in Honeywell Safety Manager systems, the Honeywell FS-TDO-1624...
Baca selengkapnya
Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .
Hubungi kami: +86 135 995 07613
Tersedia pada hari kerja antara pukul 09.00 hingga 18.00
Email kami: sales2@industriaxplc.com
Tersedia 24/7 untuk pertanyaan dan dukungan
Keterangan
Honeywell FS-TDO-1624 Digital Output Module
Configured for 24 VDC digital signal execution in Honeywell Safety Manager systems, the Honeywell FS-TDO-1624 (FS-TDO-1624 Digital Output Module) provides direct electrical switching control through 16 non-safe output channels.
Hardware Specifications
Parameter
Specification
Model
FS-TDO-1624
Brand
Honeywell
Product Type
Non-safe Digital Output Module
Origin
USA
Weight
0.3 kg
Dimensions
5.5 x 6.5 x 11.8 cm estimated shipping size
Power Consumption
5 VDC, 35 mA
Number of Output Channels
16
Output Specification
24 VDC
Maximum Output Current
100 mA per channel
Maximum Lamp Load
50 mA (1.2 W)
Maximum Load Capacitance
1 uF
Voltage Drop
< 1.2 VDC at 100 mA
Tariff Code
8537101190
Channel-to-Channel Isolation and Process Output Interface
The Honeywell FS-TDO-1624 provides 16 non-safe digital output channels for 24 VDC field device control. Therefore, the module directly drives connected actuators, indicators, and other discrete electrical loads within the Safety Manager I/O architecture.
In addition, the output stage supports defined current and capacitance limits to maintain stable switching performance. The module operates with a maximum output current of 100 mA and limits voltage drop to less than 1.2 VDC at the rated current condition.
Furthermore, Honeywell I/O modules within this platform require correct field wiring practices to maintain signal separation and minimize electrical interference. The FS-TDO-1624 focuses on discrete output execution rather than analog measurement, HART communication, or fieldbus signal processing.
Frequently Asked Questions
Q: Is the FS-TDO-1624 a safe digital output module? A: No. The FS-TDO-1624 is specified as a non-safe digital output module with 24 VDC, 16-channel switching capability.
Q: What is the maximum load current supported by each output channel? A: Each output channel supports a maximum current of 100 mA according to the provided specifications.
Q: What load types can the FS-TDO-1624 drive? A: The module supports 24 VDC discrete loads within the specified current, lamp load, and capacitance limits.
Field Installation Guidelines
Install the FS-TDO-1624 in the designated Honeywell Safety Manager I/O hardware location according to system configuration requirements.
Verify that field wiring matches the 24 VDC output rating before connecting external devices.
Separate digital output wiring from high-voltage power cables and high-noise signal sources to reduce electrical interference.
Use appropriate grounding and shielding practices when field conditions introduce electromagnetic noise.
Confirm connected loads remain within the specified 100 mA output current and 1 uF capacitance limits.
Inspect terminal connections and cable routing before system power application.