Yokogawa ASD143-P00 Analog Input Module
The Yokogawa ASD143-P00, also cataloged as the ASD143 Analog Input Module, operates as a dedicated hardware component for 4-20 mA signal acquisition within CENTUM CS 3000 and CENTUM VP systems. It converts field current inputs into digital data for process control execution and supports dual-redundant configurations for continuous loop operation.
Hardware Specifications
Parameter
Specification
Model Brand
Yokogawa
Origin
Japan
Module Type
Analog Input Module (Current Input)
Number of Channels
16 isolated
Input Signal Range
4-20 mA DC
Input Impedance
Approx. 250 Ω
A/D Conversion Resolution
16-bit
Accuracy
±0.1% full scale
System Side Isolation
Optocoupler isolation (Field-to-System)
Withstand Voltage
1500 V AC between field terminals and system
Configuration
Dual-redundant capable
Maximum Current Consumption
Dependent on system rack configuration
Weight
0.3-0.4 kg (depending on housing)
Dimensions
Standard DCS module form factor
Operating Temp
0 to 60 degC
Storage Temp
-20 to 85 degC
Power Consumption
5 V DC system power typical
Process Control Features
4-20 mA HART Loop Compatibility: Supports analog input from transmitters with standard 4-20 mA current signals and can carry HART communication signals without interruption.
Channel-to-Channel Isolation: Each input channel is electrically isolated to prevent cross-talk and ground loops between field devices and system bus.
Cold Junction Compensation (CJC): Integrated temperature sensing for compensation ensures accurate signal conversion from transmitters sensitive to ambient temperature variations.
Frequently Asked Questions
Q: What is the maximum hot-swap duration for this module? A: The ASD143-P00 can be replaced online while maintaining loop integrity; switching time is governed by DCS redundant logic but typically completes without process interruption.
Q: How is galvanic isolation implemented on this module? A: Field-to-system isolation is achieved via optocouplers on each channel to suppress surges and prevent signal interference between channels.
Q: Can firmware updates be applied without system shutdown? A: Firmware maintenance requires system-level coordination; the module supports redundant operation, but hot firmware flash must follow Yokogawa CS/VP guidelines.
Field Installation Guidelines
Mount module according to rack alignment; ensure correct slot insertion to maintain redundant bus continuity.
Connect input wiring to terminals with shielded twisted pairs; terminate shields at single-point ground near the rack.
Avoid routing high-power AC lines or heavy motor wiring adjacent to signal cables to minimize EMI.
Ensure proper airflow in the cabinet; maintain ambient temperatures within 0-60 degC.
Verify isolation gaps and field voltage limits before energizing; the module withstands 1500 V AC between field and system.