Yokogawa ALE111-S53 Ethernet Communication Module
The Yokogawa ALE111-S53, also cataloged as the ALE111 Ethernet Communication Module, operates as a dedicated hardware component for Modbus and DNP3 slave communication within CENTUM VP and CENTUM CS 3000 platforms.
Hardware Specifications
Parameter
Specification
ModelBrand
ALE111-S53
Origin
Yokogawa, Japan
Weight
Approx. 0.3 kg
Dimensions
Module compatible with SSC60, SSC50, SSC57, SNB10D racks
OperatingTemp
0 to 55 degC (standard industrial range)
PowerConsumption
0.5 A at 5 VDC
Interface
IEEE 802.3 10BASE-T, Half-duplex
Connector
RJ-45 (1 port)
TransmissionSpeed
10 Mbps
TransmissionDistance
100 m over 100 ohm twisted pair cable (unshielded)
ConnectionMethod
Point-to-point
MediaAccessControl
CSMA/CD
CommunicationFunctions
Modbus slave, DNP3 slave
NumberOfPorts
1
Channel-to-Channel Isolation
The ALE111-S53 incorporates channel-to-channel isolation to prevent cross-interference between digital communication paths. Isolation is designed to withstand up to 500 V AC, maintaining signal integrity in environments with potential ground loops or EMI from adjacent modules. Cold-junction compensation (CJC) is included for temperature-sensitive devices connected via the module, ensuring accurate analog signal interpretation when used with DCS analog input/output expansions.
Frequently Asked Questions
Q: Can the ALE111-S53 be replaced while the FCS is online? A: Yes, the module supports hot-swap replacement. Ensure the FCS is in a stable state and communication cables are secured to prevent transient errors during replacement.
Q: What is the maximum segment distance for 10BASE-T communication? A: The module supports a maximum of 100 m per segment over 100 ohm unshielded twisted pair cable between the module and hub or other network devices.
Q: How many devices can be connected per ALE111-S53 module? A: Up to 32 subsystem devices can be addressed per module, with a maximum of 4000 words for data input/output.
Field Installation Guidelines
Mount the ALE111-S53 on approved rack positions (SSC60, SSC50, SSC57, SNB10D) with secure locking.