Lebih dari 100.000 Suku Cadang PLC, DCS, Drive, TSI & MRO Tersedia Pelajari lebih lanjut

ADR541-P00 | Yokogawa CENTUM Relay Output Module

ADR541-P00 | Yokogawa CENTUM Relay Output Module

Formulir produk

Yokogawa ADR541-P00 CENTUM Relay Output Module Configured for relay contact signal switching and field device actuation in CENTUM control networks,... Baca selengkapnya

SKU: ADR541-P00
Negara asal: JAPAN

      100% Asli dan Autentik

    Butuh stok banyak? Hubungi kami .

      100% Baru, Siap kirim

    Butuh stok banyak? Hubungi kami .

      Dukungan Pengembalian Dana, Layanan 7X24 jam

    Dukungan Pengembalian Dana, Layanan 7X24jam, Hubungi kami .

      Hubungi kami: +86 135 995 07613

    Tersedia pada hari kerja antara pukul 09.00 hingga 18.00

      Email kami: sales2@industriaxplc.com

    Tersedia 24/7 untuk pertanyaan dan dukungan

    Keterangan

    Yokogawa ADR541-P00 CENTUM Relay Output Module

    Configured for relay contact signal switching and field device actuation in CENTUM control networks, the Yokogawa ADR541-P00 (ADR541 Relay Output Module) provides direct electrical execution through 16 isolated relay output channels. The module supports status output, pulse width output, and time-proportioning output functions for external loads connected to the control system.

    Suffix Breakdown & Model Matrix

    Suffix Element Specification
    -P Pulse width output function and time-proportioning output function
    0 Without status display; no explosion protection
    0 Basic type

    Hardware Specifications

    Parameter Specification
    Model Brand Yokogawa
    Origin Japan
    Weight Approx. 0.30 kg
    Power Consumption Maximum current consumption 780 mA at 5 V DC
    Module Type Relay Output Module
    Series CENTUM
    Number of Channels 16 channels
    Isolation Type Channel-to-system isolation; commons isolated in groups of 8 channels
    Rated Applied Voltage 24 to 110 V DC, 100 to 240 V AC, 50/60 Hz
    Resistive Load Capacity 2.0 A/ch at 24 V DC, 0.4 A/ch at 110 V DC, 2.0 A/ch at 100/220 V AC
    Inductive Load Capacity 0.6 A/ch at 24 V DC, 0.1 A/ch at 110 V DC, 1.0 A/ch at 100/220 V AC
    Relay Mechanical Life Minimum 100,000 operations
    Output Response Time <= 12 ms (status output), <= 20 ms (mixed status and pulse output)
    Pulse Width Range 40 ms to 7200 s
    Pulse Width Resolution 8 ms
    Withstanding Voltage 2 kV AC for 1 minute (output to system), 1.35 kV AC for 1 minute (between commons)
    Insulation Resistance 100 MOhm or greater at 500 V DC
    External Connections Pressure clamp terminal or AKB334 dedicated cable

    Channel Isolation Characteristics

    The ADR541-P00 implements channel-to-system isolation while separating commons into two groups of eight channels. This arrangement reduces electrical interference between output groups and supports independent switching of external loads. The relay outputs can interface with field circuits associated with 4-20 mA control loops, HART-connected instruments, and discrete control devices through external interposing hardware where required by the application.

    Frequently Asked Questions

    Q: Can the ADR541-P00 directly switch both AC and DC loads?
    A: Yes. The module supports relay switching of 24 to 110 V DC loads and 100 to 240 V AC loads within the specified current ratings.

    Q: Does the module support pulse-based output functions?
    A: Yes. The ADR541-P00 provides pulse width output and time-proportioning output functions in addition to standard ON/OFF status outputs.

    Q: Are all 16 channels electrically independent?
    A: Channel-to-system isolation is provided, while every eight channels share a common minus side. Commons are isolated from each other.

    Field Installation Guidelines

    1. Verify the applied load voltage and current remain within the relay contact ratings before wiring field devices.
    2. Separate output wiring from high-energy power cables to minimize electromagnetic coupling into control circuits.
    3. Use the specified pressure clamp terminal or AKB334 cable assembly according to the installation design.
    4. Connect inductive loads using suitable suppression devices where required by site engineering standards.
    5. Confirm insulation resistance and field wiring continuity before energizing the module.
    6. Ensure cabinet grounding and shield termination practices comply with the system grounding architecture.

    Spesifikasi

    • Merek: Yokogawa

    • :

    Keuntungan

    • Keandalan tinggi di lingkungan industri

    • Mendukung operasi berkelanjutan
    • Kompatibel dengan sistem PLC/DCS utama