{"product_id":"honeywell-mu-taih13-high-level-analog-input-fta-module3","title":"Honeywell MU-TAIH13 High-Level Analog Input FTA Module","description":"\u003ch2\u003eHoneywell MU-TAIH13 High-Level Analog Input FTA Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for high-level analog signal termination in Honeywell Experion PKS and TPS\/TDC 3000 systems, the \u003cstrong\u003eHoneywell MU-TAIH13\u003c\/strong\u003e (\u003cstrong\u003eMU-TAIH13\u003c\/strong\u003e High-Level Analog Input FTA Module) provides direct physical and electrical execution for 16 differential field input channels.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMU-TAIH13\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eHigh-Level Analog Input FTA Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 50 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eSupplied through system interface, value not specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e16 differential analog input channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signal Ranges\u003c\/td\u003e\n\u003ctd\u003e4-20 mA via 250 Ohm resistor, 1-5 VDC, 0-5 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eA\/D Converter Resolution\u003c\/td\u003e\n\u003ctd\u003e16-bit converter, typically 14 bits utilized\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection Ratio\u003c\/td\u003e\n\u003ctd\u003eGreater than 70 dB from DC to 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNormal Mode Rejection Ratio\u003c\/td\u003e\n\u003ctd\u003eGreater than 32 dB at 60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Differential Input Voltage\u003c\/td\u003e\n\u003ctd\u003e+\/-30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/-0.075% of full scale at 23.5 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSampling Rate\u003c\/td\u003e\n\u003ctd\u003e4 samples\/second per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Type\u003c\/td\u003e\n\u003ctd\u003eDIN rail or dedicated FTA mounting channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity Range\u003c\/td\u003e\n\u003ctd\u003e5% to 95% relative humidity, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell Experion PKS, TPS, TDC 3000 HPM\/EHPM architecture\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Instrument Signal Interface and Isolation Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe MU-TAIH13 performs field-level analog signal termination and routing for Honeywell process control platforms. It accepts current and voltage signals from transmitters, sensors, and field instruments, while the integrated precision resistor network converts current loops into voltage measurement signals.\u003c\/p\u003e\n\u003cp\u003eFurthermore, the module supports 4-20 mA HART loop protocol applications through compatible system configurations. Channel-to-channel isolation and input protection circuits reduce interference from field wiring conditions. The termination assembly also provides loop power capability for standard 2-wire transmitters when configured within supported Honeywell I\/O architectures.\u003c\/p\u003e\n\u003cp\u003eThe module maintains analog measurement integrity through common mode rejection and normal mode noise rejection characteristics. Therefore, field signal conversion remains stable during typical industrial electrical disturbances.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the MU-TAIH13 provide direct connection for 4-20 mA field transmitters?\u003cbr\u003eA: Yes. The module supports 4-20 mA input signals through integrated 250 Ohm precision shunt resistors and provides termination for compatible field transmitters.\u003c\/p\u003e\n\u003cp\u003eQ: Is the MU-TAIH13 compatible with Honeywell Experion PKS systems?\u003cbr\u003eA: Yes. The module is designed for Honeywell Experion PKS and legacy TPS\/TDC 3000 HPM\/EHPM I\/O architectures.\u003c\/p\u003e\n\u003cp\u003eQ: Does the MU-TAIH13 support voltage input signals?\u003cbr\u003eA: Yes. The module accepts voltage input ranges including 1-5 VDC and 0-5 VDC through its analog input channels.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the MU-TAIH13 on the specified FTA mounting channel or DIN rail structure according to Honeywell system installation documentation.\u003c\/p\u003e\n\u003cp\u003eTerminate field wiring using correct polarity for differential analog inputs. Use shielded instrument cables for low-level analog signals and connect cable shields according to the site grounding standard.\u003c\/p\u003e\n\u003cp\u003eSeparate analog signal wiring from high-voltage power cables and switching circuits to reduce electromagnetic interference. Verify transmitter loop polarity, signal range configuration, and input channel assignment before system commissioning.\u003c\/p\u003e\n\u003cp\u003eConfirm that field devices operate within the specified input voltage and current ranges before applying power. Check grounding continuity and protective wiring before connecting the FTA to the control system.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44391233585240,"sku":"MU-TAIH13","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/MU-TAIH13-3.jpg?v=1784279946","url":"https:\/\/www.industriaxplc.com\/products\/honeywell-mu-taih13-high-level-analog-input-fta-module3","provider":"IndustriaX Limited","version":"1.0","type":"link"}