{"product_id":"honeywell-cc-paih01-analog-input-module","title":"Honeywell CC-PAIH01 Analog Input Module","description":"\u003ch2\u003eHoneywell CC-PAIH01 Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for high level analog signal acquisition in Honeywell Experion PKS C300 I\/O architecture, the \u003cstrong\u003eHoneywell CC-PAIH01 (CC-PAIH01 Analog Input Module)\u003c\/strong\u003e provides direct physical\/electrical execution of 16-channel process signal conversion including 4-20 mA HART loop acquisition and selective differential input handling across channels 13 through 16.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eCC-PAIH01 is a fixed configuration part number with no documented functional suffix segmentation. The alternate part number 51405038-175 represents a manufacturing or logistics cross-reference identifier aligned to the same hardware assembly. No additional functional variants are defined within the provided dataset.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-PAIH01\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eChina\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.4 kg (0 lbs 12.8 oz)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e4.6 cm x 14.0 cm x 16.0 cm (1.8 in x 5.5 in x 6.3 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e16 circuits\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Types\u003c\/td\u003e\n\u003ctd\u003e4-20 mA, HART enabled analog input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDifferential Input Support\u003c\/td\u003e\n\u003ctd\u003eChannels 13 to 16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHoneywell 4-20 mA HART Process Interface Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe CC-PAIH01 implements a 4-20 mA HART loop protocol interface for hybrid analog and digital field device communication within Honeywell Experion PKS I\/O processing. Signal acquisition is performed via channelized A\/D conversion with embedded HART modulation decoding, enabling simultaneous process variable and device diagnostic extraction on the same current loop.\u003c\/p\u003e\n\u003cp\u003eChannel-to-channel electrical separation is implemented at module level to maintain isolation boundaries between field input circuits and backplane communication bus. Differential input capability is restricted to higher-numbered channels (13-16), supporting paired signal acquisition for specific transmitter configurations requiring balanced measurement topology.\u003c\/p\u003e\n\u003cp\u003eBackplane integration is executed through C300 I\/O rack architecture, where cyclic scanning is synchronized with controller task scheduling for deterministic process data refresh.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does CC-PAIH01 support hot-swap replacement under live backplane power conditions?\u003cbr\u003eA: The module is designed for insertion into C300 I\/O racks; hot-swap capability depends on system rack configuration and backplane power segmentation. Field replacement must follow rack isolation procedures.\u003c\/p\u003e\n\u003cp\u003eQ: What is the backplane communication behavior during module reset or re-initialization?\u003cbr\u003eA: During reset, channel outputs are held in a non-updating state while backplane synchronization is re-established with the C300 controller scan cycle.\u003c\/p\u003e\n\u003cp\u003eQ: Are all 16 channels HART-capable simultaneously?\u003cbr\u003eA: Yes. HART decoding is supported across all input channels where 4-20 mA signaling is present.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eThe CC-PAIH01 shall be installed in a compatible Honeywell C300 I\/O chassis with verified backplane alignment. Field wiring must maintain shield continuity at a single grounding point per segment to avoid ground loop injection into 4-20 mA measurement circuits. Twisted pair routing is required for analog input channels, with separation from high-voltage or switching conductors to minimize electromagnetic coupling.\u003c\/p\u003e\n\u003cp\u003eChannel 13 to 16 differential input wiring must maintain matched impedance routing and equal conductor length to preserve measurement balance. Connector seating must be fully engaged to ensure stable backplane communication and prevent intermittent scan loss conditions.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44339168477272,"sku":"CC-PAIHO1","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/CC-PAIHO1-3.jpg?v=1783334421","url":"https:\/\/www.industriaxplc.com\/products\/honeywell-cc-paih01-analog-input-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}