{"product_id":"honeywell-c300-cc-ppix01-pulse-input-module","title":"Honeywell C300 | CC-PPIX01 | Pulse Input Module","description":"\u003ch2\u003eHoneywell CC-PPIX01 Pulse Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for pulse frequency acquisition in Experion C300 I\/O architecture, the \u003cstrong\u003eHoneywell CC-PPIX01 51410089-175\u003c\/strong\u003e, (\u003cstrong\u003eCC-PPIX01\u003c\/strong\u003e Pulse Input Module) provides direct physical\/electrical execution. The module processes pulse signals from field devices and converts them into rate and totalized values within a distributed control system environment. It supports 8 single-channel or 4 dual-channel configurations with frequency handling up to 100 kHz (single) and 10 kHz (dual), input voltage range of 0 to 35 VDC, and configurable rising or falling edge detection. Output handling includes 2 output channels with fast cutoff response up to 1 ms.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eNo manufacturer-defined suffix segmentation is provided for CC-PPIX01 51410089-175 beyond base model and order number association.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-PPIX01 51410089-175\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.4 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e6 x 15.5 x 14.5 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eNot specified in provided data\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot specified in provided data\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e8 single \/ 4 dual\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Channels\u003c\/td\u003e\n\u003ctd\u003e2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFrequency Range\u003c\/td\u003e\n\u003ctd\u003e0 - 100 kHz (single), 0 - 10 kHz (dual)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Voltage\u003c\/td\u003e\n\u003ctd\u003e0 - 35 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Impedance\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 70 kOhm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFast Cutoff Latency\u003c\/td\u003e\n\u003ctd\u003e1 ms max\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEdge Configuration\u003c\/td\u003e\n\u003ctd\u003eRising \/ Falling selectable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Isolation\u003c\/td\u003e\n\u003ctd\u003e1000 VDC (as specified in description)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eChannel Isolation and Pulse Integrity Processing (Honeywell Experion I\/O Behavior)\u003c\/h3\u003e\n\u003cp\u003eThe module implements channel-to-channel isolation within Experion C300 I\/O architecture using high-voltage isolation barriers rated at 1000 VDC. Pulse integrity processing supports dual-pulse metering schemes compliant with ISO 6551 Level A implementation. Signal conditioning stages perform edge validation and reject transient bounce conditions prior to frequency computation. Internal diagnostics continuously monitor channel saturation, pulse dropout, and threshold violation states during runtime acquisition cycles.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does the module support hot-swap insertion in a live backplane environment?\u003cbr\u003eA: Hot-swap capability is dependent on the Experion C300 rack configuration; the module itself maintains non-volatile configuration but requires system-level support for live insertion.\u003c\/p\u003e\n\u003cp\u003eQ: What is the backplane communication dependency for pulse accumulation processing?\u003cbr\u003eA: Pulse counting and rate calculation are executed locally within the module, while aggregated values are transferred through the C300 backplane interface.\u003c\/p\u003e\n\u003cp\u003eQ: How is dual-pulse integrity maintained for custody transfer applications?\u003cbr\u003eA: Dual-channel inputs are processed under ISO 6551 Level A logic with internal correlation checks between redundant pulse streams.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eThe module shall be installed on a compatible Experion Series C I\/O chassis with verified backplane alignment. Shielded twisted-pair cabling is required for pulse inputs, with drain wire terminated at a single-point earth ground to avoid ground loop formation. Input wiring shall maintain separation from high-voltage conductors and VFD output lines to reduce induced noise coupling. Mechanical seating must ensure full connector engagement across backplane pins without partial insertion states. Field termination should respect maximum allowable conductor length as defined by system noise immunity requirements.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44301471580248,"sku":"CC-PPIX01","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/CC-PPIX01-3.jpg?v=1782895382","url":"https:\/\/www.industriaxplc.com\/products\/honeywell-c300-cc-ppix01-pulse-input-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}