{"product_id":"ge-ic200alg430-analog-mixed-i-o-module","title":"GE IC200ALG430 Analog Mixed I\/O Module","description":"\u003ch3\u003e\u003cstrong\u003eOverview\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003eThe\u003cspan\u003e \u003c\/span\u003e\u003cstrong\u003eIC200ALG430\u003c\/strong\u003e\u003cspan\u003e \u003c\/span\u003efrom GE Fanuc Emerson VersaMax series is a compact analog mixed I\/O module designed for 4–20 mA current loop signal acquisition and output control. It integrates both input and output functionality in a single-slot module, reducing rack space while maintaining high signal integrity.\u003c\/p\u003e\n\u003cp\u003eIt is engineered for process automation systems where stable analog current transmission is required, such as flow, pressure, level measurement, and actuator positioning.\u003c\/p\u003e\n\u003ch3\u003e\u003cstrong\u003eFunctional Design\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003e4 differential analog input channels (4–20 mA)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e2 single-ended analog output channels (4–20 mA)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003e12-bit analog-to-digital and digital-to-analog conversion\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eIndependent input\/output signal processing architecture\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eChannel isolation with crosstalk suppression (~30 dB)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003ePerformance Characteristics\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eInput scan time: 0.4 ms maximum\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eOutput update time: 0.3 ms maximum\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eInput filter response: 5 ms\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eResolution: 12-bit (4096 counts)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eAccuracy at 25°C: ±0.3% typical of full scale\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eMaximum accuracy: ±0.5% full scale\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eElectrical Specifications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eInput type: 4–20 mA differential current loops\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eOutput type: 4–20 mA sourcing outputs\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eBackplane power consumption: 5 VDC, approx. 50 mA\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eExternal output power: 18–30 VDC (loop dependent)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eLogic supply: 9.6–15 VDC (nominal 12 VDC)\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eLoad resistance: up to 1250 Ω\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eCapacitive load: max 0.1 µF\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eInductive load: max 0.5 H\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eIsolation: 250 VAC continuous \/ 1500 VAC for 1 minute\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eDiagnostics and Indicators\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eFLD PWR LED indicates field-side power status\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eOK LED indicates module and system health\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDetects loss of user-side power\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eConfigurable output behavior on power loss:\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eHold last output value\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDefault safe-state output\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eApplications\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cul class=\"list-paddingleft-2\"\u003e\n\u003cli\u003e\n\u003cp\u003eProcess control loops\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eFlow, pressure, and level measurement systems\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eValve and actuator control\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003ePump and compressor monitoring\u003c\/p\u003e\n\u003c\/li\u003e\n\u003cli\u003e\n\u003cp\u003eDistributed analog I\/O systems\u003c\/p\u003e\n\u003c\/li\u003e\n\u003c\/ul\u003e\n\u003ch3\u003e\u003cstrong\u003eFAQ\u003c\/strong\u003e\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does it support voltage input signals?\u003c\/strong\u003e\u003cbr\u003eA: No, it only supports 4–20 mA current loop signals.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Are input and output channels isolated?\u003c\/strong\u003e\u003cbr\u003eA: Yes, the module provides electrical isolation between sections for improved signal stability.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is external power required for outputs?\u003c\/strong\u003e\u003cbr\u003eA: Yes, outputs require an 18–30 VDC external loop power supply.\u003c\/p\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":43988165754968,"sku":"IC200ALG430","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/IC200ALG430.jpg?v=1776074354","url":"https:\/\/www.industriaxplc.com\/products\/ge-ic200alg430-analog-mixed-i-o-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}