{"product_id":"ge-ds200tbqbg1a-input-termination-module","title":"GE DS200TBQBG1A Input Termination Module","description":"\u003ch2\u003eGE DS200TBQBG1A Input Termination Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE DS200TBQBG1A\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eDS200TBQB\u003c\/strong\u003e Input Termination Module, operates as a dedicated hardware component for analog and discrete field signal termination within the Mark V SpeedTronic turbine control system. It interfaces field wiring with the associated TCQA and TCQC processor boards through dedicated backplane connectors while providing passive signal conditioning and configurable input selection.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe available documentation identifies the functional revision but does not define an official suffix matrix beyond the hardware revision.\u003c\/p\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eModel\u003c\/th\u003e\n\u003cth\u003eDescription\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eDS200TBQBG1A\u003c\/td\u003e\n\u003ctd\u003eInput Termination Module, Functional Revision A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBase Model\u003c\/td\u003e\n\u003ctd\u003eDS200TBQB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eDS200TBQBG1A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE (General Electric)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eInput Termination Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eMark V SpeedTronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFunctional Acronym\u003c\/td\u003e\n\u003ctd\u003eTBQB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFunctional Revision\u003c\/td\u003e\n\u003ctd\u003eG1A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.73 lb\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-30 deg C to +65 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5 % to 95 % non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Blocks\u003c\/td\u003e\n\u003ctd\u003e2 barrier terminal blocks\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Capacity\u003c\/td\u003e\n\u003ctd\u003eUp to 154 field termination points (77 terminals per block)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnectors\u003c\/td\u003e\n\u003ctd\u003e3 x 34-pin and 3 x 16-pin connectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Signals\u003c\/td\u003e\n\u003ctd\u003eAnalog current, analog voltage, vibration, pulse rate, compressor discharge transmitter inputs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConfiguration\u003c\/td\u003e\n\u003ctd\u003e15 onboard jumpers for input and signal configuration\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eInstalled within GE Mark V control cabinet\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eBackplane Communication and Firmware Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe DS200TBQBG1A exchanges field signals with the associated TCQA and TCQC boards through dedicated ribbon cable connectors. Analog current, voltage, vibration, and pulse-rate signals are routed from the terminal board to the processing cores without active signal conversion on the termination module itself.\u003c\/p\u003e\n\u003cp\u003eThe board includes configurable jumper groups for selecting current or voltage analog input operation and for legacy pressure transducer configurations. Compatibility depends on the installed Mark V hardware configuration and matching control cabinet documentation.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the DS200TBQBG1A provide hot-swap capability?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e No documented hot-swap capability is provided. Installation or replacement should be performed with the associated control cabinet de-energized unless GE service documentation specifies otherwise.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What are the primary field signals accepted by this module?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e The module terminates analog current, analog voltage, vibration transducer, pulse-rate, and compressor discharge transmitter signals before forwarding them to the associated processor interface boards.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How are analog input types configured?\u003c\/strong\u003e\u003cbr\u003e\u003cstrong\u003eA:\u003c\/strong\u003e Onboard jumper groups are used to select current or voltage input operation and support specific legacy input configurations where required.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eVerify the module part number and functional revision before installation.\u003c\/li\u003e\n\u003cli\u003eMount the board only in the designated Mark V cabinet position.\u003c\/li\u003e\n\u003cli\u003eRoute analog instrumentation cables separately from AC power and motor cables.\u003c\/li\u003e\n\u003cli\u003eConnect cable shields according to the cabinet grounding practice to minimize conducted noise.\u003c\/li\u003e\n\u003cli\u003eConfirm jumper settings before energizing the control system.\u003c\/li\u003e\n\u003cli\u003eFully seat all multi-pin connectors and verify terminal screw torque after field wiring.\u003c\/li\u003e\n\u003cli\u003eInspect barrier terminals periodically for loose conductors and signs of oxidation.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":44480067698776,"sku":"DS200TBQBG1A","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/DS200TBQBG1AAA_f43d230f-130f-4800-a6db-394503f7ab93.jpg?v=1785402833","url":"https:\/\/www.industriaxplc.com\/products\/ge-ds200tbqbg1a-input-termination-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}