{"product_id":"fc-sdol-0424-honeywell-digital-output-module","title":"FC-SDOL-0424 | Honeywell | Digital Output Module","description":"\u003ch2\u003eHoneywell FC-SDOL-0424 Safe Loop-Monitored Digital Output Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for safe loop-monitored digital output execution in Honeywell safety control systems, the \u003cstrong\u003eHoneywell FC-SDOL-0424\u003c\/strong\u003e (\u003cstrong\u003eSDOL-0424\u003c\/strong\u003e Safe Loop-Monitored Digital Output Module) provides direct electrical control of 24 VDC field loads through four monitored output channels.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFC-SDOL-0424\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpare Model\u003c\/td\u003e\n\u003ctd\u003eSDOL-0424\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSafe Loop-Monitored Digital Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.14 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e2 x 19 x 12.8 cm (estimated shipping size)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TUV, UL, CSA, FM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpace Requirements\u003c\/td\u003e\n\u003ctd\u003e4 TE, 3 HE (= 4 HP, 3U)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Output Channels\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Specification\u003c\/td\u003e\n\u003ctd\u003e24 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Channel Current\u003c\/td\u003e\n\u003ctd\u003e1 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Total Module Load\u003c\/td\u003e\n\u003ctd\u003e3.6 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Load Inductance\u003c\/td\u003e\n\u003ctd\u003e0.5 H\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Load Capacitance\u003c\/td\u003e\n\u003ctd\u003e1 uF\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOverload Detection Threshold\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 10 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCold Resistance Lamp Detection\u003c\/td\u003e\n\u003ctd\u003e\u0026gt; 20 Ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Monitoring Functions\u003c\/td\u003e\n\u003ctd\u003eOpen circuit, short circuit, output wiring lead breakage detection\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDe-energization Function\u003c\/td\u003e\n\u003ctd\u003eSupports de-energization and secondary de-energization methods\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eProcess Control Loop Monitoring and Output Isolation\u003c\/h3\u003e\n\u003cp\u003eThe FC-SDOL-0424 manages four 24 VDC digital output channels with continuous loop monitoring functions. Moreover, the module detects abnormal field wiring conditions, including external output lead breakage and output short circuits.\u003c\/p\u003e\n\u003cp\u003eHoneywell designs this module for safety-oriented output switching where the controller must verify the physical state of connected field devices. The output channels support load supervision through resistance monitoring, including overload detection above 10 Ohm and cold resistance lamp detection above 20 Ohm.\u003c\/p\u003e\n\u003cp\u003eIn addition, the module applies output suppression diode functions to control inductive load behavior. The design limits electrical disturbances generated by switching loads and maintains controlled output operation within specified load parameters.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many digital output channels does the Honeywell FC-SDOL-0424 provide?\u003cbr\u003eA: The FC-SDOL-0424 provides four safe loop-monitored digital output channels, each supporting 24 VDC field output operation.\u003c\/p\u003e\n\u003cp\u003eQ: What load conditions can the FC-SDOL-0424 detect?\u003cbr\u003eA: The module detects external output wiring lead breakage, output short circuits, and overload conditions through integrated loop monitoring functions.\u003c\/p\u003e\n\u003cp\u003eQ: What are the maximum electrical load limits of each output channel?\u003cbr\u003eA: Each channel supports a maximum current of 1 A, while the complete module supports a maximum total load of 3.6 A.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the FC-SDOL-0424 in the specified Honeywell safety system rack position while maintaining the required 4 TE, 3 HE mechanical allocation.\u003c\/p\u003e\n\u003cp\u003eVerify field wiring polarity before connecting 24 VDC output circuits. Furthermore, separate output wiring from high-voltage power cables and high-current switching conductors to reduce electrical interference.\u003c\/p\u003e\n\u003cp\u003eUse appropriate shield termination practices when the connected field equipment requires signal protection. Check external loop resistance values before commissioning to confirm that the module can correctly identify open circuits and abnormal load conditions.\u003c\/p\u003e\n\u003cp\u003eConfirm that connected loads remain within the specified channel current, total module load, inductive load, and capacitive load limits before system operation.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44381454205016,"sku":"FC-SDOL-0424","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/FC-SDOL-0424.jpg?v=1784095206","url":"https:\/\/www.industriaxplc.com\/products\/fc-sdol-0424-honeywell-digital-output-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}