{"product_id":"8c-pcnt03-honeywell-series-8-c300-controller-module","title":"8C-PCNT03 | Honeywell | Series 8 C300 Controller Module","description":"\u003ch2\u003eHoneywell 8C-PCNT03 Series 8 C300 Controller Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell 8C-PCNT03 51454363-275\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003e8C-PCNT03\u003c\/strong\u003e C300 Controller Module, executes deterministic control strategies and process logic within Honeywell Experion PKS Series 8 control networks.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003e8C-PCNT03\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to +60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eSupplied through Series 8 power distribution system, value not specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eComponent Part Number\u003c\/td\u003e\n\u003ctd\u003e51454363-275\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell Experion PKS \/ Experion LX Series 8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eController Type\u003c\/td\u003e\n\u003ctd\u003eC300 Control Processor Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAssociated IOTA\u003c\/td\u003e\n\u003ctd\u003e8C-TCNTA1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl Software Environment\u003c\/td\u003e\n\u003ctd\u003eControl Execution Environment (CEE)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUplink Communication\u003c\/td\u003e\n\u003ctd\u003eDual Fault Tolerant Ethernet (FTE) ports\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eI\/O Communication\u003c\/td\u003e\n\u003ctd\u003eTwo redundant I\/O links, up to 750 kbps per link\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported I\/O Capacity\u003c\/td\u003e\n\u003ctd\u003eUp to 80 I\/O Units, 40 per I\/O link\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eExecution Period\u003c\/td\u003e\n\u003ctd\u003e50 ms to 2000 ms configurable\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eControl Capacity\u003c\/td\u003e\n\u003ctd\u003e5,500 Execution Units and 4,095 tagged objects\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnvironmental Protection\u003c\/td\u003e\n\u003ctd\u003eConformal coating for harsh industrial atmosphere applications\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Method\u003c\/td\u003e\n\u003ctd\u003eDirect installation on Series 8 IOTA assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003e4-20 mA HART and DCS Process Interface Functions\u003c\/h3\u003e\n\u003cp\u003eThe Honeywell Series 8 control architecture integrates process signal management through distributed I\/O modules connected to the C300 controller. Therefore, the controller coordinates analog and digital process execution while maintaining deterministic scan timing through the Control Execution Environment (CEE).\u003c\/p\u003e\n\u003cp\u003eThe Series 8 platform supports process instrumentation integration, including 4-20 mA HART loop protocol communication, FOUNDATION Fieldbus and Profibus PA connectivity through compatible I\/O interfaces. Additionally, channel-to-channel isolation within supported I\/O modules separates field signal paths and reduces electrical interference between measurement channels.\u003c\/p\u003e\n\u003cp\u003eThe 8C-PCNT03 focuses on controller execution rather than direct field signal conversion. It processes configured control algorithms, manages I\/O communication cycles, and maintains synchronized data exchange with the Experion supervisory layer.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the 8C-PCNT03 support redundant controller operation?\u003cbr\u003eA: Yes. The 8C-PCNT03 supports non-redundant and 1:1 redundant controller configurations when installed in compatible Series 8 architectures.\u003c\/p\u003e\n\u003cp\u003eQ: Which communication interfaces are integrated into the controller module?\u003cbr\u003eA: The module provides dual Fault Tolerant Ethernet (FTE) ports for supervisory communication and redundant I\/O links for Series 8 I\/O expansion.\u003c\/p\u003e\n\u003cp\u003eQ: Can the 8C-PCNT03 directly connect field transmitters?\u003cbr\u003eA: No. The controller does not provide direct field termination. Field devices connect through compatible Series 8 I\/O modules and IOTA assemblies.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the 8C-PCNT03 only with the specified Series 8 IOTA assembly, such as the 8C-TCNTA1.\u003c\/li\u003e\n\u003cli\u003eVerify cabinet grounding before controller installation to maintain proper electrical reference potential.\u003c\/li\u003e\n\u003cli\u003eKeep Ethernet communication cables separated from high-voltage power conductors to reduce electromagnetic interference.\u003c\/li\u003e\n\u003cli\u003eConfirm redundant communication wiring before placing the controller into service.\u003c\/li\u003e\n\u003cli\u003eUse approved firmware and CEE configuration files compatible with the installed Experion PKS or Experion LX system version.\u003c\/li\u003e\n\u003cli\u003eInspect the conformal coating condition before installation in corrosive industrial environments.\u003c\/li\u003e\n\u003cli\u003eFollow Honeywell cabinet layout requirements for power distribution, grounding, and signal routing.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44415529222232,"sku":"8C-PCNT03 51454363-275","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/8C-PCNT0351454363-275-3.jpg?v=1784705813","url":"https:\/\/www.industriaxplc.com\/products\/8c-pcnt03-honeywell-series-8-c300-controller-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}