{"product_id":"safe-digital-output-modules-honeywell-fs-tsdo-0824","title":"Safe Digital Output Modules | Honeywell FS-TSDO-0824","description":"\u003ch2\u003eHoneywell FS-TSDO-0824 Safe Digital Output Field Termination Assembly\u003c\/h2\u003e\n\u003cp\u003eConfigured for fail-safe 24 VDC digital output termination in the Honeywell Safety Manager system, the \u003cstrong\u003eHoneywell FS-TSDO-0824\u003c\/strong\u003e (\u003cstrong\u003eTSDO-0824\u003c\/strong\u003e Safe Digital Output Field Termination Assembly) provides direct electrical connection between redundant output modules and external field wiring.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eFS-TSDO-0824\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSpare Model\u003c\/td\u003e\n\u003ctd\u003eTSDO-0824\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSafe Digital Output Field Termination Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell Safety Manager \/ Fail Safe Control (FSC) platforms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.05 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e60 x 70 x 58 mm (L x W x H)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003ePassive field termination interface\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8 digital output channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Voltage Rating\u003c\/td\u003e\n\u003ctd\u003e24 VDC system architecture\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Voltage\u003c\/td\u003e\n\u003ctd\u003e36 VDC, IEC 1010 (1990), Overvoltage Category 3\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Continuous Current per Channel\u003c\/td\u003e\n\u003ctd\u003e1.5 A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMaximum Wire Diameter\u003c\/td\u003e\n\u003ctd\u003e2.5 mm2 (AWG 14)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWire Strip Length\u003c\/td\u003e\n\u003ctd\u003e7 mm (0.28 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Tightening Torque\u003c\/td\u003e\n\u003ctd\u003e0.5 Nm (0.37 ft-lb)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting Method\u003c\/td\u003e\n\u003ctd\u003eUniversal DIN EN rail snap-in mounting\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported DIN Rails\u003c\/td\u003e\n\u003ctd\u003eTS32 \/ TS35 x 7.5\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUsed Rail Length\u003c\/td\u003e\n\u003ctd\u003e61 mm (2.40 in)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Type\u003c\/td\u003e\n\u003ctd\u003eScrew terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Interconnection Cable\u003c\/td\u003e\n\u003ctd\u003eSIC-C-12 \/ SICC-0001\/Lx\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eApprovals\u003c\/td\u003e\n\u003ctd\u003eCE, TUV, UL, CSA, FM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHoneywell Safety Manager Fail-Safe Output Interface Characteristics\u003c\/h3\u003e\n\u003cp\u003eThe FS-TSDO-0824 functions as the field termination point between the SIC-C-12 system interconnection cable and external field devices. It connects eight output channels from a redundant pair of safe digital output modules to field wiring through screw terminal connections.\u003c\/p\u003e\n\u003cp\u003eMoreover, the assembly supports Honeywell SIS architectures where output signals require controlled fail-safe execution. The termination interface maintains physical separation between system-side communication wiring and external field circuits, reducing wiring complexity in safety control cabinets.\u003c\/p\u003e\n\u003cp\u003eThe FS-TSDO-0824 applies Honeywell process safety hardware design principles, including channel-to-channel isolation considerations for digital signal handling and structured connection between Safety Manager output modules and field devices.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many digital output channels does the FS-TSDO-0824 provide?\u003cbr\u003eA: The FS-TSDO-0824 provides 8 independent digital output termination channels for connection between safe output modules and field wiring.\u003c\/p\u003e\n\u003cp\u003eQ: Which interconnection cable connects the FS-TSDO-0824 to Honeywell output modules?\u003cbr\u003eA: The FS-TSDO-0824 connects through the SIC-C-12 or SICC-0001\/Lx system interconnection cable to compatible safe digital output modules.\u003c\/p\u003e\n\u003cp\u003eQ: What type of field wiring terminals are provided on the FS-TSDO-0824?\u003cbr\u003eA: The module uses screw terminals supporting field conductors up to 2.5 mm2 (AWG 14) with a specified tightening torque of 0.5 Nm.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the FS-TSDO-0824 on compatible TS32 or TS35 x 7.5 DIN EN rails using the integrated snap-in mounting mechanism.\u003c\/p\u003e\n\u003cp\u003eConnect the system-side cable interface to the designated Honeywell safe digital output module connection point. Verify cable routing to maintain separation between signal wiring and high-energy circuits.\u003c\/p\u003e\n\u003cp\u003eTerminate field conductors according to the specified wire diameter range and tighten terminal screws using the recommended torque value. Confirm polarity, channel assignment, and field device connection before system commissioning.\u003c\/p\u003e\n\u003cp\u003eMaintain appropriate cabinet grounding, shielding, and wiring segregation practices according to the installation requirements of the Honeywell Safety Manager platform.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44381918330968,"sku":"FS-TSDO-0824","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/FS-TSDO-0824-3.jpg?v=1784098521","url":"https:\/\/www.industriaxplc.com\/id\/products\/safe-digital-output-modules-honeywell-fs-tsdo-0824","provider":"IndustriaX Limited","version":"1.0","type":"link"}