{"product_id":"ics-triplex-t9802-digital-input-termination-assembly-1","title":"ICS Triplex T9802 Digital Input Termination Assembly","description":"\u003ch2\u003eICS Triplex T9802 Digital Input Termination Assembly\u003c\/h2\u003e\n\u003cp\u003eConfigured for 16-channel digital input termination in ICS Triplex safety systems, the \u003cstrong\u003eICS Triplex T9802\u003c\/strong\u003e (\u003cstrong\u003eT9802\u003c\/strong\u003e Digital Input Termination Assembly) provides field-loop termination for two T9401\/2 input modules. It supports simplex, dual, and TMR configurations while applying fused field input paths.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eT9802\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICS Triplex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Input Termination Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipment Origin\u003c\/td\u003e\n\u003ctd\u003eXiamen, China\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.14 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e13.1 x 8.4 x 3.5 cm estimated shipping size\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eMaximum 0.2 W per field loop\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eField Connections\u003c\/td\u003e\n\u003ctd\u003e16\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Modules Supported\u003c\/td\u003e\n\u003ctd\u003eTwo T9401\/2\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channel Fuses\u003c\/td\u003e\n\u003ctd\u003e50 mA, 125 V, Type T, Littelfuse\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Load\u003c\/td\u003e\n\u003ctd\u003e5.125 +\/- 0.2 % kOhm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Measurement Voltage Resolution\u003c\/td\u003e\n\u003ctd\u003e5 mV, 13 bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Range\u003c\/td\u003e\n\u003ctd\u003e18-32 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConfiguration\u003c\/td\u003e\n\u003ctd\u003eSimplex, Dual, TMR\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eSafety Instrumented System Signal Handling\u003c\/h3\u003e\n\u003cp\u003eThe T9802 terminates 16 digital field inputs and routes the signals to two supported T9401\/2 input modules. Each input channel uses a 50 mA, 125 V Type T fuse manufactured by Littelfuse. Therefore, the termination assembly provides defined protection for the individual field input paths.\u003c\/p\u003e\n\u003cp\u003eThe specified channel load is 5.125 +\/- 0.2 % kOhm, while the input measurement voltage resolution reaches 5 mV at 13 bit. In addition, each field loop has a maximum power dissipation of 0.2 W.\u003c\/p\u003e\n\u003cp\u003eThe assembly supports simplex, dual, and TMR system configurations. However, the supplied data does not specify a complete SIL certification level for the T9802 itself. System-level safety certification must therefore be verified against the applicable ICS Triplex system documentation.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many field inputs does the T9802 terminate?\u003c\/strong\u003e\u003cbr\u003eA: The T9802 provides 16 field connections for digital input signals.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Which input modules does the T9802 support?\u003c\/strong\u003e\u003cbr\u003eA: The assembly supports two T9401\/2 input modules.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What fuse specification does each input channel use?\u003c\/strong\u003e\u003cbr\u003eA: Each input channel uses a 50 mA, 125 V Type T fuse manufactured by Littelfuse.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eVerify the T9802 model and supported T9401\/2 module configuration before wiring.\u003c\/li\u003e\n\u003cli\u003eConfirm the field supply remains within the specified 18-32 V range.\u003c\/li\u003e\n\u003cli\u003eRoute field signal wiring separately from high-voltage and high-current conductors where practical.\u003c\/li\u003e\n\u003cli\u003eMaintain correct polarity and terminal identification throughout field-loop installation.\u003c\/li\u003e\n\u003cli\u003eInspect each channel fuse before commissioning and replace it only with the specified fuse type and rating.\u003c\/li\u003e\n\u003cli\u003eUse appropriate shield termination practices according to the system installation drawing.\u003c\/li\u003e\n\u003cli\u003eConfirm field-loop resistance and wiring continuity before connecting the input modules.\u003c\/li\u003e\n\u003cli\u003eFor TMR installations, follow the system-specific wiring and redundancy architecture defined by the ICS Triplex documentation.\u003c\/li\u003e\n\u003cli\u003eDo not infer operating-temperature or hot-swap limits from the termination assembly specifications when the supplied data does not define them.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ICS Triplex","offers":[{"title":"Default Title","offer_id":44547390603352,"sku":"T9802","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/T9802-3_1200x1200_2c34df60-1c18-4b68-b32a-5fdf5dd24db8.jpg?v=1786348496","url":"https:\/\/www.industriaxplc.com\/id\/products\/ics-triplex-t9802-digital-input-termination-assembly-1","provider":"IndustriaX Limited","version":"1.0","type":"link"}