{"product_id":"honeywell-mc-tdod13-digital-output-field-termination-assembly","title":"Honeywell MC-TDOD13 Digital Output Field Termination Assembly","description":"\u003ch2\u003eHoneywell MC-TDOD13 Digital Output Field Termination Assembly\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell MC-TDOD13 51304650-150\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eMC-TDOD13\u003c\/strong\u003e Digital Output Field Termination Assembly, operates as a dedicated hardware component for solid-state field signal switching within Honeywell TDC 3000 and Experion PKS DCS platforms.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eMC-TDOD13\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePart Number\u003c\/td\u003e\n\u003ctd\u003e51304650-150\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eDigital Output Field Termination Assembly\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSystem Compatibility\u003c\/td\u003e\n\u003ctd\u003eHoneywell TDC 3000, Experion PKS, PM \/ APM \/ HPM\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIOP Compatibility\u003c\/td\u003e\n\u003ctd\u003eMU\/MC-PDOX01, MU\/MC-PDOX02\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Count\u003c\/td\u003e\n\u003ctd\u003e16 digital output channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Type\u003c\/td\u003e\n\u003ctd\u003eSolid-state relay \/ DC power output\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Voltage Range\u003c\/td\u003e\n\u003ctd\u003e3 to 30 VDC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Current\u003c\/td\u003e\n\u003ctd\u003e2.0 A maximum per channel continuous\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eOptical isolation channel-to-channel and system-to-field\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFuse Protection\u003c\/td\u003e\n\u003ctd\u003e2.5 A per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRedundancy\u003c\/td\u003e\n\u003ctd\u003eNot supported\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Type\u003c\/td\u003e\n\u003ctd\u003eCompression terminals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCoating\u003c\/td\u003e\n\u003ctd\u003eConformal coated (CC)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCE Compliance\u003c\/td\u003e\n\u003ctd\u003eNon-CE compliant\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.5 kg to 1.0 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eBoard Size B, approximately 307 mm length\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95% RH, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eDependent on field load current and output activation state\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eDCS Digital Output Isolation and Field Signal Control\u003c\/h3\u003e\n\u003cp\u003eThe MC-TDOD13 provides direct electrical switching between Honeywell DCS output logic and connected field devices. It uses optical isolation to separate control-side circuits from field-side loads. Therefore, the assembly reduces the influence of field voltage disturbances, ground potential differences, and switching noise.\u003c\/p\u003e\n\u003cp\u003eThe unit supports 16 solid-state output channels for DC field devices. In addition, each output channel includes individual fuse protection and supports direct control of devices such as solenoid valves, interposing relays, contactors, and motor starter interfaces.\u003c\/p\u003e\n\u003cp\u003eHoneywell DCS digital output assemblies typically maintain compatibility with process instrumentation standards, including isolated field wiring practices and 4-20 mA HART, FOUNDATION Fieldbus, or Profibus PA interfaces within associated system architectures. However, the MC-TDOD13 itself functions as a discrete output termination device and does not provide analog communication protocol conversion.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the MC-TDOD13 support redundant output operation?\u003cbr\u003eA: No. The MC-TDOD13 does not support redundant channel configuration or automatic output transfer functions.\u003c\/p\u003e\n\u003cp\u003eQ: What type of field loads can the MC-TDOD13 drive?\u003cbr\u003eA: The assembly supports DC loads within the 3 to 30 VDC range, including low-power solenoids, relays, and contactor control circuits.\u003c\/p\u003e\n\u003cp\u003eQ: Does the module provide electrical isolation between channels?\u003cbr\u003eA: Yes. The assembly provides optical isolation between channels and between the DCS control logic side and field device side.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the MC-TDOD13 inside an approved Honeywell I\/O termination cabinet or compatible enclosure.\u003c\/li\u003e\n\u003cli\u003eUse the specified compression terminal wiring method and verify conductor tightness before system startup.\u003c\/li\u003e\n\u003cli\u003eSeparate digital output wiring from high-voltage power cables to reduce electromagnetic interference.\u003c\/li\u003e\n\u003cli\u003eConnect cable shields according to the site grounding standard and avoid multiple grounding points on shielded signal cables.\u003c\/li\u003e\n\u003cli\u003eVerify field load voltage and current requirements before connecting external devices to each output channel.\u003c\/li\u003e\n\u003cli\u003eConfirm fuse ratings and field protection devices before energizing the output circuits.\u003c\/li\u003e\n\u003cli\u003eInspect conformal coating condition when installing the assembly in humid, dusty, or corrosive environments.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44494964654168,"sku":"MC-TDOD13 51304650-150","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/MC-TDOD13-51304650-150-3_1200x1200_e7362043-dd50-40ad-ba70-f79e235146c5.jpg?v=1785751760","url":"https:\/\/www.industriaxplc.com\/id\/products\/honeywell-mc-tdod13-digital-output-field-termination-assembly","provider":"IndustriaX Limited","version":"1.0","type":"link"}