{"product_id":"cc-paih02-honeywell-c300-hart-analog-input","title":"CC-PAIH02 | Honeywell | C300 Hart Analog Input","description":"\u003ch2\u003eHoneywell CC-PAIH02 C300 HART Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eHoneywell CC-PAIH02\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eCC-PAIH02\u003c\/strong\u003e HART Analog Input Module, operates as a dedicated hardware component for acquisition of 4-20 mA and voltage-based process signals within the Honeywell Experion PKS C300 I\/O architecture. The module digitizes up to 16 field input channels while maintaining concurrent HART digital communication over the same loop interface for bidirectional parameter access and diagnostics.\u003c\/p\u003e\n\u003ch3\u003eSuffix Breakdown \u0026amp; Model Matrix\u003c\/h3\u003e\n\u003cp\u003eThe model designation \u003cstrong\u003eCC-PAIH02\u003c\/strong\u003e does not contain documented functional suffix segmentation beyond its base catalog identifier. No verified manufacturer-published sub-variant decoding is available for this part number.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eCC-PAIH02\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eHoneywell\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.3kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 deg C to 60 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eApprox. 60 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eHART Analog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannel Count\u003c\/td\u003e\n\u003ctd\u003e16 channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Types\u003c\/td\u003e\n\u003ctd\u003e4-20 mA, 1-5 V, 0-5 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Mode\u003c\/td\u003e\n\u003ctd\u003eSingle-ended \/ differential configuration support\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHART Protocol\u003c\/td\u003e\n\u003ctd\u003eSupported on field loops\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eHoneywell 4-20 mA HART Loop Integration Characteristics\u003c\/h3\u003e\n\u003cp\u003eWithin the Honeywell Series C I\/O system, the CC-PAIH02 operates on a multiplexed analog-digital loop structure where 4-20 mA process current is sampled concurrently with HART FSK modulation signals. The module performs channel-level signal conditioning and digitization prior to backplane transmission toward the C300 controller. Channel-to-channel electrical separation is implemented at the I\/O termination assembly level to reduce cross-channel coupling during mixed-signal acquisition. HART communication frames are passed transparently to higher-level asset management layers without interrupting analog conversion cycles.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003eQ: Does the CC-PAIH02 support hot-swap replacement under energized conditions?\u003cbr\u003eA: The module is designed for removal and insertion at the Series C I\/O level; however, safe replacement requires adherence to system-defined hot-swap procedures to maintain backplane integrity and avoid loop disturbance.\u003c\/p\u003e\n\u003cp\u003eQ: How is HART data handled during continuous analog sampling?\u003cbr\u003eA: HART FSK signals are demodulated in parallel with 4-20 mA acquisition, allowing simultaneous analog conversion and digital field device communication without loop interruption.\u003c\/p\u003e\n\u003cp\u003eQ: What is the backplane power dependency of the module?\u003cbr\u003eA: The module draws operational power from the Series C backplane supply; load distribution is managed at the I\/O chassis level and must remain within controller power budget limits.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eThe CC-PAIH02 shall be installed on a compatible Honeywell Series C I\/O termination assembly with verified grounding continuity between chassis earth and field cable shields. Shield termination should be performed at a single-point ground reference to prevent circulating currents across analog input loops. Field wiring for 4-20 mA channels must maintain loop resistance within transmitter compliance limits to ensure proper current regulation. Signal cables carrying HART communication should be routed separately from high-voltage switching conductors to minimize induced noise coupling. All module insertion and removal actions shall follow system-defined maintenance isolation procedures to avoid transient backplane disturbance.\u003c\/p\u003e","brand":"Honeywell","offers":[{"title":"Default Title","offer_id":44339126501464,"sku":"CC-PAIHO2","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/CC-PAIHO2-3.jpg?v=1783332789","url":"https:\/\/www.industriaxplc.com\/id\/products\/cc-paih02-honeywell-c300-hart-analog-input","provider":"IndustriaX Limited","version":"1.0","type":"link"}