{"product_id":"ai830-3bse008519r1-rtd-input-module-abb-s800-i-o","title":"AI830 3BSE008519R1  RTD Input Module ABB S800 I\/O","description":"\u003ch2\u003eABB AI830 3BSE008518R1 RTD Input Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for RTD temperature signal acquisition in ABB System 800xA and S800 I\/O networks, the \u003cstrong\u003eABB AI830 3BSE008518R1\u003c\/strong\u003e (\u003cstrong\u003eAI830\u003c\/strong\u003e RTD Input Module) provides direct physical measurement of resistive temperature elements through 8 analog input channels.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eAI830 3BSE008518R1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eABB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eRTD Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eSweden\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.24 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e4.5 x 10.5 x 12 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003e1.6 W\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eModule Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Specification\u003c\/td\u003e\n\u003ctd\u003e3-wire RTD: Pt100, Cu10, Ni100, Ni120 and resistive potentiometer\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNumber of Channels\u003c\/td\u003e\n\u003ctd\u003e8\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Cycle Time\u003c\/td\u003e\n\u003ctd\u003e150 + 9 ms\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRated Insulation Voltage\u003c\/td\u003e\n\u003ctd\u003e50 V\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDielectric Test Voltage\u003c\/td\u003e\n\u003ctd\u003e500 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCMRR at 50 Hz \/ 60 Hz\u003c\/td\u003e\n\u003ctd\u003e\u0026gt;60 dB\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCurrent Consumption +5 V Modulebus\u003c\/td\u003e\n\u003ctd\u003e70 mA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eABB S800 I\/O Backplane Integration and I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eThe AI830 operates as an ABB S800 I\/O analog input component with direct Modulebus communication. It supports configurable channel parameters, allowing each RTD input channel to operate independently according to the connected sensor type.\u003c\/p\u003e\n\u003cp\u003eThe module performs signal linearization and temperature conversion into Centigrade or Fahrenheit values internally. In addition, the MainsFreq parameter configures the 50 Hz or 60 Hz notch filter cycle to reduce power frequency interference during measurement.\u003c\/p\u003e\n\u003cp\u003eThe AI830 follows ABB industrial control architecture principles, including I\/O density scaling through modular channel allocation and standardized backplane communication interfaces.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Which temperature sensors can the ABB AI830 3BSE008518R1 measure?\u003cbr\u003eA: The AI830 supports 3-wire RTD sensors including Pt100, Cu10, Ni100, Ni120, and resistive potentiometers.\u003c\/p\u003e\n\u003cp\u003eQ: Does each AI830 input channel have independent configuration capability?\u003cbr\u003eA: Yes. Each of the 8 RTD input channels can be configured individually for the connected resistive measurement element.\u003c\/p\u003e\n\u003cp\u003eQ: What installation requirement applies to RTD sensor wiring?\u003cbr\u003eA: All connected RTD elements must remain isolated from ground to maintain correct measurement performance.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the AI830 module in the designated ABB S800 I\/O rack position according to system configuration requirements.\u003c\/li\u003e\n\u003cli\u003eConnect RTD sensors using 3-wire wiring methods and maintain correct terminal assignments.\u003c\/li\u003e\n\u003cli\u003eKeep RTD signal cables separated from high voltage and high current conductors to reduce electrical interference.\u003c\/li\u003e\n\u003cli\u003eEnsure all RTD sensors remain isolated from ground unless the system design specifies another grounding method.\u003c\/li\u003e\n\u003cli\u003eVerify channel configuration parameters before commissioning temperature measurements.\u003c\/li\u003e\n\u003cli\u003eCheck Modulebus communication status after installation to confirm correct module recognition.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ABB","offers":[{"title":"Default Title","offer_id":44627713654872,"sku":"AI830 3BSE008519R1","price":99.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/AI830-3BSE008519R1-3_1200x1200_1728994b-ff52-4667-8f37-9b0a99b34e41.jpg?v=1787216274","url":"https:\/\/www.industriaxplc.com\/id\/products\/ai830-3bse008519r1-rtd-input-module-abb-s800-i-o","provider":"IndustriaX Limited","version":"1.0","type":"link"}