{"product_id":"ics-triplex-t8480c-trusted-tmr-analogue-output-module","title":"ICS Triplex T8480C Trusted TMR Analogue Output Module","description":"\u003ch2\u003eICS Triplex T8480C Trusted TMR Analogue Output Module\u003c\/h2\u003e\n\u003cp\u003eConfigured for 4-20 mA DC analogue output execution in a Trusted TMR control system, the \u003cstrong\u003eICS Triplex T8480C\u003c\/strong\u003e (\u003cstrong\u003eT8480C\u003c\/strong\u003e Trusted TMR Analogue Output Module) provides four output channels with 16-bit resolution and 1500 V AC isolation.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eT8480C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eICS Triplex\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eTrusted TMR Analogue Output Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eChannels\u003c\/td\u003e\n\u003ctd\u003e4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Signal\u003c\/td\u003e\n\u003ctd\u003e4-20 mA DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVoltage Option\u003c\/td\u003e\n\u003ctd\u003e0-10 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eResolution\u003c\/td\u003e\n\u003ctd\u003e16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAccuracy\u003c\/td\u003e\n\u003ctd\u003e+\/- 0.1% of full scale\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eLoad Compliance\u003c\/td\u003e\n\u003ctd\u003e0-750 ohm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eUpdate Rate\u003c\/td\u003e\n\u003ctd\u003e100 ms per channel\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003e1500 V AC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Supply\u003c\/td\u003e\n\u003ctd\u003e5 V DC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eTrusted rack\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUSA\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1.32 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003e3 x 30.3 x 26.5 cm\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +70 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity\u003c\/td\u003e\n\u003ctd\u003e0-95% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTariff Code\u003c\/td\u003e\n\u003ctd\u003e8537101190\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShipment Location\u003c\/td\u003e\n\u003ctd\u003eXiamen, China\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTrusted TMR and Galvanic Isolation\u003c\/h3\u003e\n\u003cp\u003eThe T8480C forms part of the ICS Triplex Trusted safety control architecture. Its analogue output channels provide electrical control signals for connected field devices while maintaining 1500 V AC isolation.\u003c\/p\u003e\n\u003cp\u003eThe module supports four channels and provides 16-bit output resolution. Therefore, the control system can issue analogue commands with defined numerical resolution across the configured output range.\u003c\/p\u003e\n\u003cp\u003eThe 4-20 mA DC output supports loads from 0 to 750 ohm. The module also specifies a 0-10 V DC voltage option. Each channel updates at a stated rate of 100 ms.\u003c\/p\u003e\n\u003cp\u003eThe Trusted TMR architecture supports fault-tolerant signal processing through redundant processing paths. However, the supplied data does not define the specific TMR voting implementation or SIL certification details for this individual module, so those parameters should be verified against the applicable Trusted system manual.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions (FAQ)\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: How many analogue output channels does the T8480C provide?\u003c\/strong\u003e\u003cbr\u003eA: The T8480C provides four analogue output channels.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What output ranges does the supplied specification identify?\u003c\/strong\u003e\u003cbr\u003eA: The specification identifies 4-20 mA DC output and a 0-10 V DC voltage option.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: What load can the 4-20 mA output drive?\u003c\/strong\u003e\u003cbr\u003eA: The specified load compliance range is 0-750 ohm.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the T8480C in the specified Trusted rack and secure the module according to the rack installation procedure.\u003c\/li\u003e\n\u003cli\u003eVerify the rack power supply before inserting the module.\u003c\/li\u003e\n\u003cli\u003eRoute analogue signal wiring separately from high-voltage switching and high-current power conductors where practical.\u003c\/li\u003e\n\u003cli\u003eUse suitable shielded cable for low-level analogue signals when the installation environment presents significant electromagnetic interference.\u003c\/li\u003e\n\u003cli\u003eTerminate cable shields according to the plant grounding and instrumentation wiring standard. Avoid creating unintended ground loops.\u003c\/li\u003e\n\u003cli\u003eVerify the connected load before commissioning each 4-20 mA output channel.\u003c\/li\u003e\n\u003cli\u003eConfirm field wiring polarity and terminal assignments against the applicable Trusted system documentation before energizing the circuit.\u003c\/li\u003e\n\u003cli\u003eKeep signal wiring mechanically secured and provide adequate strain relief at termination points.\u003c\/li\u003e\n\u003cli\u003eDo not infer hot-swap capability from the supplied specifications. Confirm the permitted insertion and removal procedure in the applicable Trusted rack documentation.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"ICS Triplex","offers":[{"title":"Default Title","offer_id":44547431923800,"sku":"T8480C","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/T8480C-3_1200x1200_f815deb1-772b-4220-b90a-4b52f1f073d8.jpg?v=1786349236","url":"https:\/\/www.industriaxplc.com\/ar\/products\/ics-triplex-t8480c-trusted-tmr-analogue-output-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}