{"product_id":"ge-is230stcih6a-simplex-thermocouple-input-terminal-board","title":"GE IS230STCIH6A Simplex Thermocouple Input Terminal Board","description":"\u003ch2\u003eGE IS230STCIH6A Simplex Thermocouple Input Terminal Board\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eGE IS230STCIH6A\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eIS230STCIH6A\u003c\/strong\u003e Simplex Thermocouple Input Terminal Board, operates as a dedicated hardware component for thermocouple temperature signal acquisition within GE Mark VIe Speedtronic control systems. The board provides conditioned analog temperature inputs from field sensors to turbine controller processing channels.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eIS230STCIH6A\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGE\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.5 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-30 deg C to +65 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eMark VIe Speedtronic Control System\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eSimplex Thermocouple Input Terminal Boards\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Channels\u003c\/td\u003e\n\u003ctd\u003e12 thermocouple input channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Thermocouple Types\u003c\/td\u003e\n\u003ctd\u003eType E, J, K, S, T\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSignal Conditioning\u003c\/td\u003e\n\u003ctd\u003eEMI filtering, linearization, and scaling\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCold Junction Compensation\u003c\/td\u003e\n\u003ctd\u003eIntegrated CJC circuitry\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eChannel-to-channel and channel-to-ground isolation\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eTerminal Interface\u003c\/td\u003e\n\u003ctd\u003eBarrier terminal strips for thermocouple wiring\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temperature\u003c\/td\u003e\n\u003ctd\u003e-40 deg C to +85 deg C\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eHumidity Range\u003c\/td\u003e\n\u003ctd\u003e5% to 95% non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eMounting\u003c\/td\u003e\n\u003ctd\u003eStandard Mark VIe rack slot\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCompliance\u003c\/td\u003e\n\u003ctd\u003eIEC 60584 thermocouple standard\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eIndustrial Control Signal Processing and I\/O Density Scaling\u003c\/h3\u003e\n\u003cp\u003eThe IS230STCIH6A provides thermocouple signal termination and conditioning functions within the GE Mark VIe control architecture. The board receives temperature signals from field thermocouples, applies cold junction compensation, linearization, and filtering, then transfers processed input data through the Mark VIe I\/O interface.\u003c\/p\u003e\n\u003cp\u003eThe terminal board supports I\/O density scaling by integrating 12 temperature measurement channels into a simplex hardware assembly. Firmware flash compatibility depends on the installed GE Mark VIe controller, I\/O pack configuration, and system revision.\u003c\/p\u003e\n\u003cp\u003eChannel isolation separates thermocouple measurement circuits from adjacent electrical paths, reducing signal interference during temperature acquisition. The input processing design supports deterministic temperature feedback collection for turbine monitoring and protection logic.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: How many thermocouple inputs are available on the IS230STCIH6A?\u003cbr\u003eA: The IS230STCIH6A provides 12 thermocouple input channels in simplex configuration.\u003c\/p\u003e\n\u003cp\u003eQ: Which thermocouple types are supported by the board?\u003cbr\u003eA: The board supports Type E, J, K, S, and T thermocouple sensors.\u003c\/p\u003e\n\u003cp\u003eQ: What function does the CJC circuit perform on the IS230STCIH6A?\u003cbr\u003eA: The cold junction compensation circuit corrects reference junction effects during thermocouple temperature measurement processing.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cp\u003eInstall the IS230STCIH6A in the specified GE Mark VIe rack position and confirm connector engagement before applying system power.\u003c\/p\u003e\n\u003cp\u003eUse compatible thermocouple extension cables and maintain correct polarity between field sensors and terminal connections. Route thermocouple wiring separately from high-current conductors, switching devices, and power supply cables to reduce electromagnetic interference.\u003c\/p\u003e\n\u003cp\u003eConnect cable shields according to cabinet grounding practices. Verify terminal assignments, sensor types, and channel configuration before commissioning.\u003c\/p\u003e\n\u003cp\u003eInspect terminal blocks, field wiring insulation, and connector conditions during maintenance activities. Avoid unnecessary cable loops and maintain separation between temperature measurement circuits and electrical noise sources.\u003c\/p\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":44407808098392,"sku":"IS230STCIH6A","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/IS230SNCIH2A1_26ac3f15-890a-4fc3-b028-b7e563fae72e.jpg?v=1784624380","url":"https:\/\/www.industriaxplc.com\/ar\/products\/ge-is230stcih6a-simplex-thermocouple-input-terminal-board","provider":"IndustriaX Limited","version":"1.0","type":"link"}