{"product_id":"ge-ds200tceag1a-emergency-trip-board","title":"GE DS200TCEAG1A Emergency Trip Board","description":"\u003ch2\u003eGE DS200TCEAG1A Emergency Trip Board\u003c\/h2\u003e\n\u003cp\u003eConfigured for emergency turbine trip execution in the GE Mark V Speedtronic control system, the \u003cstrong\u003eGE DS200TCEAG1A\u003c\/strong\u003e (\u003cstrong\u003eDS200TCEAG1\u003c\/strong\u003e Emergency Trip Board) provides direct hardwired protective signal processing for overspeed detection, flame monitoring, and trip relay actuation across redundant R, S, and T control cores.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eDS200TCEAG1A \/ DS200TCEAG1\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eGeneral Electric (GE)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eUnited States\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e1 lbs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e-30 deg C to +65 deg C (-22 deg F to +149 deg F)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eMark V Speedtronic\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eEmergency Trip Board\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eFunctional Role\u003c\/td\u003e\n\u003ctd\u003eHardwired protective trip logic interface\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Signals\u003c\/td\u003e\n\u003ctd\u003eMagnetic speed pickup signals and flame detection signals\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOutput Interface\u003c\/td\u003e\n\u003ctd\u003eTrip relay outputs and emergency shutdown solenoid control\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRedundancy Architecture\u003c\/td\u003e\n\u003ctd\u003eTMR (R, S, T triplicated voting cores)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDiagnostics\u003c\/td\u003e\n\u003ctd\u003eStatus LED indicators and test point arrays\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eConnections\u003c\/td\u003e\n\u003ctd\u003eRibbon cable headers, multi-pin terminal connectors, configurable jumpers\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003eTMR Trip Logic and Protective Signal Execution\u003c\/h3\u003e\n\u003cp\u003eThe DS200TCEAG1A operates within the GE Mark V Speedtronic TMR architecture using independent R, S, and T protective cores. The board supports two-out-of-three (2oo3) voting logic for emergency trip decisions, allowing hardware-level execution of shutdown commands when abnormal turbine operating conditions are detected.\u003c\/p\u003e\n\u003cp\u003eThe board processes high-speed pulse inputs from turbine speed sensors and interfaces with flame monitoring circuits. Its circuitry provides direct control of emergency trip relays and fuel shutoff solenoids without depending solely on primary software execution paths.\u003c\/p\u003e\n\u003cp\u003eThe module incorporates industrial control diagnostic functions including LED status indication and test point access for signal verification during commissioning and maintenance activities.\u003c\/p\u003e\n\u003ch3\u003eBackplane Bus Communication and Firmware Compatibility\u003c\/h3\u003e\n\u003cp\u003eThe DS200TCEAG1A is designed as a dedicated Mark V control board with fixed hardware functions rather than a general programmable I\/O module. Communication with the turbine control system is performed through the Mark V board-level interconnection structure using dedicated connectors and ribbon cable interfaces.\u003c\/p\u003e\n\u003cp\u003eFirmware and hardware compatibility must be maintained according to the installed Mark V system configuration. Replacement boards require matching hardware revision and application compatibility before integration into the control rack.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003eQ: Does the DS200TCEAG1A support hot-swap replacement during turbine operation?\u003cbr\u003eA: The board is designed as a Mark V protective control component. Replacement procedures require system-specific shutdown and maintenance instructions because trip circuitry is directly connected to emergency shutdown functions.\u003c\/p\u003e\n\u003cp\u003eQ: What type of signals are processed by the DS200TCEAG1A?\u003cbr\u003eA: The board accepts turbine protection related inputs including magnetic speed pickup signals and flame detection signals, then executes hardware trip outputs through relay and solenoid drive circuits.\u003c\/p\u003e\n\u003cp\u003eQ: How does the board provide redundancy support?\u003cbr\u003eA: The DS200TCEAG1A interfaces with the Mark V R, S, and T protective cores and participates in TMR 2oo3 voting logic for emergency trip decisions.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eVerify board part number and hardware revision before installation into the Mark V control rack.\u003c\/li\u003e\n\u003cli\u003eConfirm connector alignment for ribbon cable headers and multi-pin terminal connections before energizing the system.\u003c\/li\u003e\n\u003cli\u003eMaintain proper cable routing separation between low-level sensor wiring and high-energy switching circuits.\u003c\/li\u003e\n\u003cli\u003eUse approved grounding practices for rack chassis connections and signal cable shielding.\u003c\/li\u003e\n\u003cli\u003eVerify speed pickup and flame detection wiring polarity according to the turbine control system drawings.\u003c\/li\u003e\n\u003cli\u003ePerform LED status checks and test point verification after installation before returning the protective circuit to service.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"General Electric","offers":[{"title":"Default Title","offer_id":44484753784920,"sku":"DS200TCEAG1A","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/DS200TCEAG1ADB.jpg?v=1785487502","url":"https:\/\/www.industriaxplc.com\/ar\/products\/ge-ds200tceag1a-emergency-trip-board","provider":"IndustriaX Limited","version":"1.0","type":"link"}