{"product_id":"bmxart0814-modicon-x80-schneider-electric-analog-input-module","title":"BMXART0814 Modicon X80 Schneider Electric Analog Input Module","description":"\u003ch2\u003eSchneider Electric BMXART0814 Modicon X80 Analog Input Module\u003c\/h2\u003e\n\u003cp\u003eThe \u003cstrong\u003eSchneider Electric BMXART0814\u003c\/strong\u003e, also cataloged as the \u003cstrong\u003eBMXART0814\u003c\/strong\u003e Analog Input Module, operates as a dedicated hardware component for low-level temperature signal acquisition within the Modicon X80 automation platform. The module provides eight isolated analog input channels supporting thermocouple and temperature probe measurement with sigma-delta conversion and integrated diagnostic indication.\u003c\/p\u003e\n\u003ch3\u003eHardware Specifications\u003c\/h3\u003e\n\u003cfigure class=\"table\"\u003e\n\u003ctable\u003e\n\u003cthead\u003e\n\u003ctr\u003e\n\u003cth\u003eParameter\u003c\/th\u003e\n\u003cth\u003eSpecification\u003c\/th\u003e\n\u003c\/tr\u003e\n\u003c\/thead\u003e\n\u003ctbody\u003e\n\u003ctr\u003e\n\u003ctd\u003eModel\u003c\/td\u003e\n\u003ctd\u003eBMXART0814\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eBrand\u003c\/td\u003e\n\u003ctd\u003eSchneider Electric\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSeries\u003c\/td\u003e\n\u003ctd\u003eModicon X80\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eProduct Type\u003c\/td\u003e\n\u003ctd\u003eAnalog Input Module\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Inputs\u003c\/td\u003e\n\u003ctd\u003e8 isolated channels\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eInput Level\u003c\/td\u003e\n\u003ctd\u003eLow level\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eElectrical Connection\u003c\/td\u003e\n\u003ctd\u003eTwo 40-pin connectors\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog\/Digital Conversion\u003c\/td\u003e\n\u003ctd\u003eSigma-delta, 16-bit\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eAnalog Resolution\u003c\/td\u003e\n\u003ctd\u003e15 bits + sign\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eSupported Measurements\u003c\/td\u003e\n\u003ctd\u003eThermocouple, temperature probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCold Junction Compensation\u003c\/td\u003e\n\u003ctd\u003eExternal Pt100 probe\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDigital Filter\u003c\/td\u003e\n\u003ctd\u003eFirst-order digital filtering\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eNominal Read Cycle\u003c\/td\u003e\n\u003ctd\u003e200 ms (thermocouple); 400 ms (temperature probe)\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePermitted Input Overload\u003c\/td\u003e\n\u003ctd\u003e+\/- 7.5 V with specified measurement ranges\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCommon Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e120 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDifferential Mode Rejection\u003c\/td\u003e\n\u003ctd\u003e60 dB at 50\/60 Hz\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStatus Indicators\u003c\/td\u003e\n\u003ctd\u003eRUN, channel diagnostic, ERR, I\/O LEDs\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIsolation\u003c\/td\u003e\n\u003ctd\u003eChannel-to-channel isolated\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Altitude\u003c\/td\u003e\n\u003ctd\u003e0 to 2000 m; up to 5000 m with derating\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOperating Temp\u003c\/td\u003e\n\u003ctd\u003e0 to 60 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStorage Temp\u003c\/td\u003e\n\u003ctd\u003e-40 to 85 degC\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eRelative Humidity\u003c\/td\u003e\n\u003ctd\u003e5% to 95% at 55 degC, non-condensing\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eIP Rating\u003c\/td\u003e\n\u003ctd\u003eIP20\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eVibration Resistance\u003c\/td\u003e\n\u003ctd\u003e3 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eShock Resistance\u003c\/td\u003e\n\u003ctd\u003e30 gn\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eCertifications\u003c\/td\u003e\n\u003ctd\u003eCE, UL, CSA, EAC, RCM, Merchant Navy\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eStandards\u003c\/td\u003e\n\u003ctd\u003eEN 61131-2, EN 61000-6-2, EN 61000-6-4, EN 61010-2-201\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eEnvironmental Classification\u003c\/td\u003e\n\u003ctd\u003eIEC 60721-3-3 Class 3C3, 3C4\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eWeight\u003c\/td\u003e\n\u003ctd\u003e0.165 kg\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eDimensions\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003ePower Consumption\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003ctr\u003e\n\u003ctd\u003eOrigin\u003c\/td\u003e\n\u003ctd\u003eNot specified\u003c\/td\u003e\n\u003c\/tr\u003e\n\u003c\/tbody\u003e\n\u003c\/table\u003e\n\u003c\/figure\u003e\n\u003ch3\u003ePLC Backplane Communication and I\/O Density\u003c\/h3\u003e\n\u003cp\u003eThe BMXART0814 exchanges measurement data through the Modicon X80 backplane architecture. Eight isolated input channels allow temperature acquisition without increasing signal interaction between adjacent channels. Sigma-delta conversion and first-order digital filtering are implemented to process low-level analog inputs before transmission to the controller over the backplane bus.\u003c\/p\u003e\n\u003ch3\u003eFrequently Asked Questions\u003c\/h3\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Does the module provide channel isolation?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. Each of the eight analog input channels is electrically isolated, reducing interference between measurement circuits.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Is cold junction compensation integrated into the module?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: The module performs cold junction compensation using an external Pt100 probe connected according to the application requirements.\u003c\/p\u003e\n\u003cp\u003e\u003cstrong\u003eQ: Can the module measure both thermocouples and temperature probes?\u003c\/strong\u003e\u003c\/p\u003e\n\u003cp\u003eA: Yes. The specified nominal conversion cycle is 200 ms for thermocouple measurement and 400 ms for temperature probe measurement.\u003c\/p\u003e\n\u003ch3\u003eField Installation Guidelines\u003c\/h3\u003e\n\u003cul\u003e\n\u003cli\u003eInstall the module only in a compatible Modicon X80 rack with power removed before insertion or removal unless the system documentation explicitly permits online replacement.\u003c\/li\u003e\n\u003cli\u003eRoute thermocouple and low-level analog wiring separately from power and motor cables to minimize induced electrical noise.\u003c\/li\u003e\n\u003cli\u003eConnect cable shields according to the plant grounding practice and avoid multiple shield grounding points unless specified by the control system design.\u003c\/li\u003e\n\u003cli\u003eInstall the external Pt100 sensor for cold junction compensation as specified by the wiring documentation.\u003c\/li\u003e\n\u003cli\u003eMaintain adequate enclosure ventilation so the ambient operating temperature remains within the specified 0 to 60 degC range.\u003c\/li\u003e\n\u003c\/ul\u003e","brand":"Schneider Electric","offers":[{"title":"Default Title","offer_id":44278298083416,"sku":"BMXART0814","price":100.0,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0670\/2039\/0488\/files\/BMXART0814-3.jpg?v=1782438741","url":"https:\/\/www.industriaxplc.com\/ar\/products\/bmxart0814-modicon-x80-schneider-electric-analog-input-module","provider":"IndustriaX Limited","version":"1.0","type":"link"}